Zennio -ZCL8H230V2- 8-6-2- Output- 230V - Pemanasan- Aktuator - LOGO

Zennio ZCL8H230V2 8/6/2 Output 230V Pemanasan Actuator

Zennio -ZCL8H230V2- 8-6-2- Output- 230V -Pemanasan- Aktuator - GAMBAR PRODUK

Informasi produk

KOTAK Pemanasan 230V 8X/6X/2X v2

Pemanasan BOX 230V 8X / 6X / 2X v2 saka Zennio minangka aktuator KNX khusus pemanasan sing dilengkapi output independen 8 / 6 / 2 (gumantung model) kanggo ngontrol katup 230V. Iki dirancang kanggo ngontrol katup elektromekanis lan nawakake sawetara fitur sing luar biasa:

  • 8 / 6 / 2 output sing bisa dikonfigurasi kanggo katup kontrol
  • 8 / 6 / 2 input multi-tujuan, bisa dikonfigurasi minangka probe suhu utawa input binar (tombol, switch, sensor)
  • Input daya tunggal 230 VAC kanggo kabeh output
  • 8/6/2 termostat independen
  • 10 fungsi logika multi-operasi sing bisa disesuaikan
  • Operasi manual / pengawasan output liwat tombol push on-board lan LED
  • Kabar deg-degan utawa periodik sing isih urip

Pandhuan Panggunaan Produk

Kanggo miwiti nggunakake HeatingBOX 230V 8X/6X/2X v2, tindakake langkah ing ngisor iki:

Wiwitan lan Power Loss
Sajrone wiwitan, piranti bisa nindakake tumindak tartamtu adhedhasar konfigurasi. Hubungi manual pangguna kanggo rincian babagan ngatur prilaku piranti nalika miwiti. Yen ana gangguan daya bis, piranti bakal ngganggu tumindak sing ditundha lan nyimpen statuse supaya bisa pulih sawise daya dipulihake.

Konfigurasi

Kanggo ngatur HeatingBOX 230V 8X/6X/2X v2, tindakake langkah iki:

  1. Impor database sing cocog ing ETS (Perangkat Lunak Alat Teknik).
  2. Tambah piranti menyang topologi proyek sing dikarepake.
  3. Ngakses tab Parameter piranti kanggo miwiti proses konfigurasi.

Sawise ngimpor database sing cocog ing ETS lan nambahake piranti menyang topologi proyek sing dikarepake, proses konfigurasi diwiwiti kanthi ngetik tab Parameter piranti.

Konfigurasi Umum

Ing layar Umum, sampeyan bisa ngaktifake utawa mateni fungsi sing dibutuhake. Parameter ing ngisor iki kasedhiya:

  • Detak Jantung (Kabar Urip Berkala): Parameter iki ngidini integrator nggabungake obyek siji-bit menyang proyek (Obyek [Detak Jantung] Kanggo Dikirim `1′) sing bakal dikirim sacara periodik kanthi nilai 1 kanggo menehi kabar yen piranti isih bisa digunakake ( isih urip).

Saka layar "Umum" bisa ngaktifake / mateni kabeh fungsi sing dibutuhake.

PARAMETERISASI ETS

Zennio -ZCL8H230V2- 8-6-2- Output- 230V - Pemanasan- Aktuator - 01

Layar umum

  • Detak Jantung (Kabar Urip Berkala) [dipateni / diaktifake] 1: parameter iki ngidini integrator nggabungake obyek siji-bit menyang proyek kasebut ("Obyek [Detak Jantung] Kanggo Kirim '1'") sing bakal dikirim sacara periodik kanthi nilai "1" kanggo menehi kabar yen piranti isih bisa digunakake (isih urip).

Zennio -ZCL8H230V2- 8-6-2- Output- 230V - Pemanasan- Aktuator - 02

Detak Jantung (Kabar Urip Berkala).
1 Nilai standar saben parameter bakal disorot biru ing dokumen iki, kaya ing ngisor iki: [standar/pilihan liyane].
Cathetan: ngirim pisanan sawise download utawa bis Gagal njupuk Panggonan karo wektu tundha nganti 255 detik, kanggo nyegah kakehan bis. Kiriman ing ngisor iki cocog karo wektu sing disetel.
Obyek Recovery Piranti (Kirim 0 lan 1) [pateni / diaktifake]: parameter iki ngidini integrator ngaktifake rong obyek komunikasi anyar ("[Detak jantung] Piranti Recovery"), sing bakal dikirim menyang bis KNX kanthi nilai "0" lan " 1" saben piranti wiwit operasi (contoneample, sawise bus gagal listrik). Sampeyan bisa nemtokake wektu tundha tartamtu [0…255] kanggo ngirim.

Zennio -ZCL8H230V2- 8-6-2- Output- 230V - Pemanasan- Aktuator - 03

Ngirim obyek Indikasi ing bus voltage pulih.
Cathetan: Sawise download utawa bus gagal, ngirim njupuk Panggonan karo wektu tundha nganti 6,35 detik plus wektu tundha parameterised, kanggo nyegah kakehan.

  • Thermostat [patèn / aktif]: mbisakake utawa mateni tab "Thermostat" ing wit ing sisih kiwa. Waca bagean 2.2 kanggo rincian.
  • Fungsi Logika [dipateni / diaktifake]: ngaktifake utawa mateni tab "Fungsi Logika" ing wit ing sisih kiwa. Waca bagean 2.3 kanggo rincian.
  • Input [pateni / aktif]: mbisakake utawa mateni tab "Input" ing wit ing sisih kiwa. Waca bagean 2.4 kanggo rincian.
  • Kontrol Pemanasan [aktif]: paramèter mung diwaca kanggo mbuktekake manawa tab "Kontrol Pemanasan" tansah diaktifake ing wit tab ing sisih kiwa. Waca bagean 2.5 kanggo rincian.
  • Kontrol Manual [pateni / aktif]: mbisakake utawa mateni tab "Control Manual" ing wit ing sisih kiwa. Waca bagean 2.6 kanggo rincian.

THERMOSTATS
HeatingBOX ngetrapake termostat Zennio 8 / 6 / 2 (gumantung model) sing bisa diaktifake lan dikonfigurasi kanthi mandiri. Mangga deleng manual pangguna khusus "Zennio Thermostat" (kasedhiya ing bagean produk ing homepage Zennio, www.zennio.com) kanggo informasi rinci babagan fungsi lan konfigurasi paramèter sing gegandhengan.

FUNGSI LOGIKA
Modul iki ndadekake iku bisa kanggo nindakake operasi numerik lan binar menyang nilai mlebu ditampa saka bis KNX, lan ngirim asil liwat obyek komunikasi liyane khusus aktif kanggo maksud iki. HeatingBOX bisa ngetrapake nganti 10 fungsi sing beda-beda lan mandiri, saben-saben bisa dikustomisasi lan kalebu nganti 4 operasi berturut-turut. Eksekusi saben fungsi bisa gumantung ing kondisi sing bisa dikonfigurasi, sing bakal dievaluasi saben-saben fungsi kasebut dipicu liwat obyek komunikasi sing bisa dikonfigurasi. Asil sawise nglakokake operasi fungsi kasebut uga bisa dievaluasi miturut kahanan tartamtu lan banjur dikirim (utawa ora) menyang bis KNX, sing bisa ditindakake saben-saben fungsi kasebut dieksekusi, sacara periodik utawa mung nalika asil beda saka pungkasan. siji. Mangga deleng manual pangguna khusus "Fungsi Logika" (kasedhiya ing bagean produk ing homepage Zennio, www.zennio.com) kanggo informasi rinci babagan fungsi lan konfigurasi paramèter sing gegandhengan.

INPUT
HeatingBOX nggabungake 8/6/2 input analog/digital, saben bisa dikonfigurasi minangka:

  • Input binar, kanggo sambungan tombol push utawa switch / sensor.
  • Temperature Probe, kanggo nyambungake sensor suhu saka Zennio utawa NTC probe saka pihak katelu (sing terakhir mbutuhake konfigurasi paramèter ing ETS).

INPUT BINARI
Mangga deleng manual pangguna tartamtu "Input Biner", kasedhiya ing bagean produk, ing Zennio websitus (www.zennio.com).
PROBE SUHU
Mangga deleng manual pangguna tartamtu "Temperature Probe", kasedhiya ing bagean produk, ing Zennio websitus (www.zennio.com).

KONTROL PANAS
Aktuator HeatingBOX nggabungake output 8/6/2, saben-saben bisa ngontrol siji utawa sawetara katup pemanasan ing 230V. Mangga deleng manual pangguna khusus "Kontrol Pemanasan" (kasedhiya ing bagean produk ing homepage Zennio, www.zennio.com) kanggo informasi rinci babagan fungsi lan konfigurasi paramèter sing gegandhengan.

KONTROL MANUAL

HeatingBOX ngidini ngontrol output liwat tombol push ing sisih ndhuwur piranti. Saben output nduweni tombol push sing gegandhengan. Operasi manual bisa ditindakake kanthi rong cara, dijenengi Test On Mode (kanggo tujuan testing sajrone konfigurasi piranti) lan Test Off Mode (kanggo panggunaan normal, kapan wae). Apa loro-lorone, mung siji utawa ora ana mode iki sing kasedhiya perlu parameterisasi ing ETS. Kajaba iku, bisa ngaktifake obyek binar tartamtu kanggo ngunci lan mbukak kunci kontrol manual nalika runtime.

Cathetan:

  • Mode Test Off bakal aktif (kajaba wis dipatèni dening parameter) sawise download utawa reset tanpa perlu aktivasi tartamtu - pushbuttons bakal nanggapi kanggo pangguna mencet saka wiwitan.
  • Kosok baline, ngalih menyang mode Test On (kajaba dipateni dening parameter) kudu ditindakake kanthi mencet tombol Prog./Test (paling sethithik telung detik), nganti LED ora abang maneh lan dadi kuning. Wiwit wektu iku, yen tombol diluncurake, lampu LED bakal tetep ijo kanggo konfirmasi manawa piranti wis ngalih saka mode Test Off menyang mode Test On. Sawisé iku, penet tambahan bakal nguripake LED kuning lan banjur mati, sawise tombol dirilis. Kanthi cara iki, piranti metu saka mode Test On. Elinga yen uga bakal ninggalake mode iki yen gagal daya bis dumadi.
  • Kontrol manual output dimaksudaké kanggo nindakake ngalih on / off, independen saka cara kontrol diatur (siji-bit utawa siji-bait). Ing tembung liyane, ngidini nyoba mbukak lan nutup katup, nanging posisi penengah ora bisa ditindakake.

Tes Mode Mati
Ing Mode Test Off, output bisa dikontrol liwat obyek komunikasi lan tombol push nyata sing ana ing sisih ndhuwur piranti. Uga, sajrone mode kontrol manual iki, prentah kontrol sing ditampa dening bis bakal terus dianalisis lan dieksekusi. Yen tombol push ing output aktif dipencet, output bakal tumindak kaya pesenan kanggo mbukak utawa nutup tutup wis ditampa liwat obyek komunikasi sing cocog lan uga bakal ngirim obyek status yen dibutuhake. Babagan fungsi kunci lan weker, piranti bakal tumindak ing mode Test Off kaya biasane. Pencet tombol sajrone mode iki meh padha karo resepsi pesenan sing cocog saka bis KNX.

Test On Mode
Sawise ngetik mode Test On, mung bisa ngontrol output liwat tombol push on-board. Pesenan kontrol sing ditampa liwat obyek komunikasi bakal diabaikan. Pencet cendhak utawa dawa tombol bakal ngowahi status on-off output. LED bakal madhangi ijo nalika tombol ditahan. Fungsi kunci lan weker uga pesenan sing ditampa saka bis KNX ora bakal mengaruhi status output nalika piranti ana ing mode Test On. Objek status ora bakal dikirim menyang bis, uga. Kosok baline, weker lan obyek kunci bakal dievaluasi maneh sawise metu saka mode Test On, saengga owah-owahan apa wae sing kedadeyan ing Test On bakal dianggep nalika lunga.
penting: piranti dikirim saka pabrik karo loro mode manual (Test Off lan Test On) aktif kanthi gawan.
Kanggo fitur teknis sing rinci, proses instalasi, lan prosedur keamanan, waca Datasheet sing kasedhiya karo kemasan asli piranti utawa bukak www.zennio.com.
Yen sampeyan butuh pitulung luwih utawa dhukungan teknis, bukak https://support.zennio.com/.

UPDATE DOKUMEN

Versi Owah-owahan Kaca
[1.5]_b Piranti anyar: KOTAK Pemanasan 230V 6X / 2X v2.

PAMBUKA

Pemanasan KOTAK

HeatingBOX saka Zennio minangka aktuator KNX khusus sing dilengkapi pemanasan, kanthi output independen 8/6/2 (gumantung model) kanggo ngontrol katup 230V.
Fitur sing paling pinunjul yaiku:

  • / 6/2 output configurable kanggo kontrol klep electromechanical.
  • 8/6/2 input serbaguna, bisa dikonfigurasi minangka:
    • Temperatur probe (kanthi kamungkinan kanggo parameterisasi probe pribadi).
    • Input biner (yaiku, pushbuttons, switch, sensor).
  • Input daya tunggal 230 VAC kanggo kabeh output.
  • 8/6/2 termostat independen.
  • 10 customisable, fungsi logika multi-operasi.
  • Operasi manual / pengawasan output liwat tombol push on-board lan LED.
  • Detak jantung utawa kabar "isih-urip" periodik.

START-UP lan POWER LOSS
Sajrone wiwitan piranti lan gumantung saka konfigurasi, sawetara tumindak tartamtu bisa ditindakake. Kanggo example, integrator bisa nyetel apa output kudu ngganti menyang posisi tartamtu lan apa piranti ngirim ngirim obyek tartamtu kanggo bis sawise Recovery daya. Mangga deleng bagean sabanjure dokumen iki kanggo rincian liyane. Ing sisih liya, nalika ana gangguan listrik bis, piranti kasebut bakal ngganggu tumindak sing ditundha, lan bakal nylametake kahanane supaya bisa dipulihake sawise sumber daya dipulihake. Kanggo entuk informasi rinci babagan fitur teknis piranti iki, uga babagan proses instalasi lan prosedur keamanan, waca Lembar Data sing cocog, sing dibundel karo kemasan asli piranti kasebut lan uga kasedhiya ing www.zennio.com.

PARAMETERISASI ETS
Sawise ngaktifake "Kontrol Manual" ing layar Konfigurasi (pirsani bagean 2.1), tab anyar bakal digabung menyang wit tab ing sisih kiwa.

Zennio -ZCL8H230V2- 8-6-2- Output- 230V - Pemanasan- Aktuator - 04
Kontrol Manual.
Mung rong paramèter yaiku:

  • Mode [Pateni / Mung karo Mode Test Off / Mung karo Test Mode On / Test Off Mode + Test On Mode]. Gumantung saka pilihan, piranti bakal ngidini nggunakake kontrol manual ing mode Test Off, Test On, utawa loro-lorone. Elinga, kaya sing wis kasebut sadurunge, nggunakake mode Test Off ora mbutuhake tumindak khusus, nalika ngoper menyang mode Test On mbutuhake menet tombol Prog./Test.
  • Kunci Kontrol Manual [pateni / aktif]: kajaba parameter ing ndhuwur wis "Disabled", parameter Lock Manual Control menehi prosedur opsional kanggo ngunci kontrol manual ing runtime. Yen kothak centhang iki diaktifake, obyek "Kontrol Manual Kunci" dadi katon, uga rong parameter liyane:
    • Nilai [0 = Mbukak kunci; 1 = Kunci / 0 = Kunci; 1= Mbukak kunci]: nemtokake manawa kunci kontrol manual / bukak kunci kudu ditindakake nalika nampa (liwat obyek kasebut) nilai "0" lan "1", utawa kosok balene.
    • Initialization [Mbukak kunci / Dikunci / Nilai Terakhir (Sadurunge Bus Gagal)]: nyetel carane kontrol manual kudu tetep sawise wiwitan piranti (sawise download ETS utawa bus gagal listrik).

LAMPIRAN I. OBJEK KOMUNIKASI

  • "Rentang fungsional" nuduhake nilai sing, kanthi bebas saka nilai liyane sing diidini bis miturut ukuran obyek, bisa uga ana gunane utawa duwe makna tartamtu amarga spesifikasi utawa watesan saka standar KNX utawa program aplikasi. dhewe.'
Nomer Ukuran Aku/O Gendéra Tipe Data (DPT) Range Fungsional jeneng Fungsi
1 1 bit I C - W - - DPT_Ngalih 0/1 Kunci Kontrol Manual 0 = Mbukak kunci; 1 = Ngunci
1 bit I C - W - - DPT_Ngalih 0/1 Kunci Kontrol Manual 0 = Kunci; 1 = Mbukak kunci
2 1 Byte I C - W - - DPT_SceneControl 0-63; 128-191 [Thermostat] Pemandangan 0 – 63 (Nglakokake 1 – 64); 128 – 191
(Simpen 1 – 64)
3, 41, 79, 117, 155, 193, 231, 269 2 bita I C – WTU DPT_Value_Temp -273,00º – 670433,28º [Tx] Sumber Suhu 1 Suhu Sensor njaba
4, 42, 80, 118, 156, 194, 232, 270 2 bita I C – WTU DPT_Value_Temp -273,00º – 670433,28º [Tx] Sumber Suhu 2 Suhu Sensor njaba
5, 43, 81, 119, 157, 195, 233, 271 2 bita O CR - T - DPT_Value_Temp -273,00º – 670433,28º [Tx] Suhu Efektif Suhu Kontrol Efektif
6, 44, 82, 120, 158, 196, 234, 272  

1 Byte

 

I

 

C - W - -

 

DPT_HVACMode

1 = Panglipur 2 = Siaga 3 = Ekonomi
4 = Proteksi
[Tx] Mode Khusus Mode HVAC 1-Byte
7, 45, 83, 121, 159, 197, 235, 273 1 bit I C - W - - DPT_Ack 0/1 [Tx] Mode Khusus: Nyaman 0 = Ora ana apa-apa; 1 = Pemicu
1 bit I C - W - - DPT_Ngalih 0/1 [Tx] Mode Khusus: Nyaman 0 = Mati; 1 = Ing
8, 46, 84, 122, 160, 198, 236, 274 1 bit I C - W - - DPT_Ack 0/1 [Tx] Mode Khusus: Siaga 0 = Ora ana apa-apa; 1 = Pemicu
1 bit I C - W - - DPT_Ngalih 0/1 [Tx] Mode Khusus: Siaga 0 = Mati; 1 = Ing
9, 47, 85, 123, 161, 199, 237, 275 1 bit I C - W - - DPT_Ack 0/1 [Tx] Mode Khusus: Ekonomi 0 = Ora ana apa-apa; 1 = Pemicu
1 bit I C - W - - DPT_Ngalih 0/1 [Tx] Mode Khusus: Ekonomi 0 = Mati; 1 = Ing
10, 48, 86, 124, 162, 200, 238, 276 1 bit I C - W - - DPT_Ack 0/1 [Tx] Mode Khusus: Proteksi 0 = Ora ana apa-apa; 1 = Pemicu
1 bit I C - W - - DPT_Ngalih 0/1 [Tx] Mode Khusus: Proteksi 0 = Mati; 1 = Ing
11, 49, 87, 125, 163, 201, 239, 277 1 bit I C - W - - DPT_Window_Door 0/1 [Tx] Status Jendela (Input) 0 = Ditutup; 1 = Bukak
12, 50, 88, 126, 164, 202, 240, 278 1 bit I C - W - - DPT_Pemicu 0/1 [Tx] Kenyamanan Prolongation 0 = Ora ana apa-apa; 1 = Panglipur Wektu
13, 51, 89, 127, 165, 203, 241, 279 1 Byte O CR - T - DPT_HVACMode 1 = Panglipur 2 = Siaga 3 = Ekonomi 4 = Proteksi [Tx] Status Mode Khusus Mode HVAC 1-Byte
2 bita I C - W - - DPT_Value_Temp -273,00º – 670433,28º [Tx] Setpoint Input Setpoint Thermostat
14, 52, 90, 128, 166, 204, 242, 280 2 bita I C - W - - DPT_Value_Temp -273,00º – 670433,28º [Tx] Setpoint dhasar Setpoint Referensi
15, 53, 91, 129, 167, 205, 243, 281 1 bit I C - W - - DPT_Langkah 0/1 [Tx] Langkah Setpoint 0 = Ngurangi Setpoint; 1 = Tambah Setpoint
16, 54, 92, 130, 168, 206, 244, 282 2 bita I C - W - - DPT_Value_Tempd -671088,64º – 670433,28º [Tx] Setpoint Offset Nilai Ngambang Offset
17, 55, 93, 131, 169, 207, 245, 283 2 bita O CR - T - DPT_Value_Temp -273,00º – 670433,28º [Tx] Status Setpoint Setpoint Saiki
18, 56, 94, 132, 170, 208, 246, 284 2 bita O CR - T - DPT_Value_Temp -273,00º – 670433,28º [Tx] Status Setpoint Dasar Setpoint Dasar Saiki
19, 57, 95, 133, 171, 209, 247, 285 2 bita O CR - T - DPT_Value_Tempd -671088,64º – 670433,28º [Tx] Status Offset Setpoint Setpoint Offset Saiki
20, 58, 96, 134, 172, 210, 248, 286 1 bit I C - W - - DPT_Reset 0/1 [Tx] Setpoint Reset Reset Setpoint menyang Default
1 bit I C - W - - DPT_Reset 0/1 [Tx] Offset Reset Reset Offset
21, 59, 97, 135, 173, 211, 249, 287 1 bit I C - W - - DPT_Panas_Adem 0/1 [Tx] Mode 0 = Kelangan; 1 = Panas
22, 60, 98, 136, 174, 212, 250, 288 1 bit O CR - T - DPT_Panas_Adem 0/1 [Tx] Status Mode 0 = Kelangan; 1 = Panas
23, 61, 99, 137, 175, 213, 251, 289 1 bit I C - W - - DPT_Ngalih 0/1 [Tx] Urip/Mati 0 = Mati; 1 = Ing
24, 62, 100, 138, 176, 214, 252, 290 1 bit O CR - T - DPT_Ngalih 0/1 [Tx] Status On/Off 0 = Mati; 1 = Ing
25, 63, 101, 139, 177, 215, 253, 291 1 bit Aku/O CRW-- DPT_Ngalih 0/1 [Tx] Sistem Utama (Keren) 0 = Sistem 1; 1 = Sistem 2
26, 64, 102, 140, 178, 216, 254, 292 1 bit Aku/O CRW-- DPT_Ngalih 0/1 [Tx] Sistem Utama (Panas) 0 = Sistem 1; 1 = Sistem 2
27, 65, 103, 141, 179, 217, 255, 293 1 bit I C - W - - DPT_Aktifake 0/1 [Tx] Aktifake/Pateni Sistem Sekunder (Keren) 0 = Pateni; 1 = Aktifake
28, 66, 104, 142, 180, 218, 256, 294 1 bit I C - W - - DPT_Aktifake 0/1 [Tx] Aktifake/Pateni Sistem Sekunder (Panas) 0 = Pateni; 1 = Aktifake
29, 35, 67, 73, 105, 111, 143, 149, 181, 187, 219, 225, 257, 263, 295, 301 1 Byte O CR - T - DPT_Scaling 0% – 100s [Tx] [Sx] Variabel Kontrol (Keren) Kontrol PI (Terus)
30, 36, 68, 74, 106, 112, 144, 150, 182, 188, 220, 226, 258, 264, 296, 302 1 Byte O CR - T - DPT_Scaling 0% – 100% [Tx] [Sx] Variabel Kontrol (Panas) Kontrol PI (Terus)
1 Byte O CR - T - DPT_Scaling 0% – 100% [Tx] [Sx] Variabel Kontrol Kontrol PI (Terus)
31, 37, 69, 75, 107, 113, 145, 151, 183, 189, 221, 227, 259, 265, 297, 303 1 bit O CR - T - DPT_Ngalih 0/1 [Tx] [Sx] Variabel Kontrol (Keren) 2-Titik Kontrol
1 bit O CR - T - DPT_Ngalih 0/1 [Tx] [Sx] Variabel Kontrol (Keren) Kontrol PI (PWM)
1 bit O CR - T - DPT_Ngalih 0/1 [Tx] [Sx] Variabel Kontrol (Panas) 2-Titik Kontrol
32, 38, 70, 76, 108, 114, 146, 152, 184, 190, 222, 228, 260, 266, 298, 304 1 bit O CR - T - DPT_Ngalih 0/1 [Tx] [Sx] Variabel Kontrol (Panas) Kontrol PI (PWM)
1 bit O CR - T - DPT_Ngalih 0/1 [Tx] [Sx] Variabel Kontrol 2-Titik Kontrol
1 bit O CR - T - DPT_Ngalih 0/1 [Tx] [Sx] Variabel Kontrol Kontrol PI (PWM)
33, 39, 71, 77, 109, 115, 147, 153, 185, 191, 223, 229, 261, 267, 299, 305 1 bit O CR - T - DPT_Ngalih 0/1 [Tx] [Sx] Negara PI (Keren) 0 = Sinyal PI 0%; 1 = Sinyal PI
Luwih saka 0%
34, 40, 72, 78, 110, 116, 148, 154, 186, 192, 224, 230, 262, 268, 300, 306 1 bit O CR - T - DPT_Ngalih 0/1 [Tx] [Sx] Status PI (Panas) 0 = Sinyal PI 0%; 1 = Sinyal PI
Luwih saka 0%
1 bit O CR - T - DPT_Ngalih 0/1 [Tx] [Sx] Negara PI 0 = Sinyal PI 0%; 1 = Sinyal PI
Luwih saka 0%
307, 308, 309, 310, 311, 312, 313, 314, 315, 316, 317, 318, 319, 320, 321, 322, 323, 324, 325, 326, 327, 328 329, 330, 331, 332, 333, 334, 335 1 bit I C - W - - DPT_Bool 0/1 [LF] (1-Bit) Entri Data x Entri Data Biner (0/1)
339, 340, 341, 342, 343, 344, 345, 346, 347, 348, 349, 350, 351, 352, 353, 354 1 Byte I C - W - - DPT_Value_1_Ucount 0 – 255 [LF] (1-Byte) Entri Data x 1-Byte Entri Data (0-255)
355, 356, 357, 358, 359, 360, 361, 362, 363, 364, 365, 366, 367, 368, 369, 370 2 bita I C - W - - DPT_Value_2_Ucount 0 – 65535 [LF] (2-Byte) Entri Data x 2-Byte Entri Data
371, 372, 373, 374, 375, 376, 377, 378 4 bita I C - W - - DPT_Value_4_Count -2147483648 –

2147483647

[LF] (4-Byte) Entri Data x 4-Byte Entri Data
379, 380, 381, 382, ​​383, 384, 385, 386, 387, 388 1 bit O CR - T - DPT_Bool 0/1 [LF] Fungsi x – Hasil (1-Bit) Boolean
1 Byte O CR - T - DPT_Value_1_Ucount 0 – 255 [LF] Fungsi x – Hasil (1-Byte) Ora ditandatangani
2 bita O CR - T - DPT_Value_2_Ucount 0 – 65535 [LF] Fungsi x – Hasil (2-Byte) Ora ditandatangani
4 bita O CR - T - DPT_Value_4_Count -2147483648 –

2147483647

[LF] Fungsi x – Hasil (4-Byte) mlebu
1 Byte O CR - T - DPT_Scaling 0% – 100% [LF] Fungsi x – Hasil (1-Byte) Persentage
2 bita O CR - T - DPT_Value_2_Count -32768 – 32767 [LF] Fungsi x – Hasil (2-Byte) mlebu
2 bita O CR - T - 9.xxx -671088,64 – 670433,28 [LF] Fungsi x – Hasil (2-Byte) Ngambang
389 1 bit O CR - T - DPT_Bool 0/1 [HC] Kabeh Katup Ditutup 0 = Palsu; 1 = Bener
1 bit O CR - T - DPT_Bool 0/1 [HC] Kabeh Katup Ditutup 0 = Bener; 1 = Palsu
390 1 Byte O CR - T - DPT_Scaling 0% – 100% [HC] Maks. Nilai Kontrol (Output) 0 – 100 %
391 1 Byte I C - W - - DPT_Scaling 0% – 100% [HC] Maks. Nilai Kontrol (Input) 0 – 100 %
392, 404, 416, 428, 440, 452, 464, 476 1 bit O CR - T - DPT_Weker 0/1 [HCx] Kesalahan Short Circuit 0 = Ora Ana Kasalahan; 1 = Kasalahan
393, 441 1 bit O CR - T - DPT_Weker 0/1 [HCx-x] Kasalahan kakehan 0 = Ora Ana Kasalahan; 1 = Kasalahan
394, 406, 418, 430, 442, 454, 466, 478 1 bit I C - W - - DPT_Aktifake 0/1 [HCx] Kunci 0 = Mbukak kunci; 1 = Ngunci
395, 407, 419, 431, 443, 455, 467, 479 1 bit I C - W - - DPT_Weker 0/1 [HCx] Weker 0 = Ora Weker; 1 = Weker
1 bit I C - W - - DPT_Weker 0/1 [HCx] Weker 0 = Weker; 1 = Ora Weker
396, 408, 420, 432, 444, 456, 468, 480 1 bit I C - W - - DPT_Weker 0/1 [HCx] Weker x 0 = Ora Weker; 1 = Weker
1 bit I C - W - - DPT_Weker 0/1 [HCx] Weker x 0 = Weker; 1 = Ora Weker
397, 409, 421, 433, 445, 457, 469, 481 1 bit I C - W - - DPT_Ack 0/1 [HCx] Unfreeze Weker Weker = Ora Weker + Unfreeze (1) -> Weker Pungkasi
1 bit I C - W - - DPT_Ack 0/1 [HCx] Unfreeze Weker Weker = Weker 2 = Ora Weker + Mbukak beku (1) -> Weker Akhir
398, 410, 422, 434, 446, 458, 470, 482 1 bit O CR - T - DPT_Bool 0/1 [HCx] Nilai Kontrol - Kesalahan 0 = Ora Ana Kasalahan; 1 = Kasalahan
399, 411, 423, 435, 447, 459, 471, 483 1 bit O CR - T - DPT_Negara 0/1 [HCx] Proteksi Anti-Seize 0 = Ora aktif; 1 = Aktif
400, 412, 424, 436, 448, 460, 472, 484 1 bit I C - W - - DPT_Ngalih 0/1 [HCx] Nilai Kontrol - 1 bit 0 = Tutup Katup; 1 = Katup mbukak
1 bit I C - W - - DPT_OpenClose 0/1 [HCx] Nilai Kontrol - 1 bit 0 = Katup Bukak; 1 = Tutup Katup
401, 413, 425, 437, 449, 461, 473, 485 1 bit O CR - T - DPT_Ngalih 0/1 [HCx] Nilai Kontrol – 1 bit (Status) 0 = Ditutup; 1 = Bukak
1 bit O CR - T - DPT_OpenClose 0/1 [HCx] Nilai Kontrol – 1 bit (Status) 0 = mbukak; 1 = Ditutup
402, 414, 426, 438, 450, 462, 474, 486 1 Byte I C - W - - DPT_Scaling 0% – 100% [HCx] Nilai Kontrol - 1 byte 0 – 100 %
403, 415, 427, 439, 451, 463, 475, 487 1 Byte O CR - T - DPT_Scaling 0% – 100% [HCx] Nilai Kontrol – 1 byte (Status) 0 – 100 %
488 1 bit O CR - T - DPT_Bool 0/1 [HC] Kunci Sirkuit Cekak/Kakehan 0 = Mbukak kunci; 1 = Dikunci
489 1 bit C--T- DPT_Pemicu 0/1 [Detak Jantung] Obyek sing arep Dikirim '1' Ngirim '1' sacara periodik
490 1 bit C--T- DPT_Pemicu 0/1 [Detak jantung] Recovery piranti Kirimi 0
491 1 bit C--T- DPT_Pemicu 0/1 [Detak jantung] Recovery piranti Kirimi 1
492, 498, 504, 510, 516, 522, 528, 534 1 bit I C - W - - DPT_Aktifake 0/1 [Ix] Kunci Input 0 = Mbukak kunci; 1 = Ngunci
493, 499, 505, 511, 517, 523, 529, 535 1 bit C--T- DPT_Ngalih 0/1 [Ix] [Short Press] 0 Kiriman saka 0
1 bit C--T- DPT_Ngalih 0/1 [Ix] [Short Press] 1 Kiriman saka 1
1 bit I C – WT – DPT_Ngalih 0/1 [Ix] [Short Press] 0/1 Ngalih Ngalih 0/1
1 bit C--T- DPT_UpDown 0/1 [Ix] [Short Press] Pindhah munggah Rana Ngirim 0 (Up)
1 bit C--T- DPT_UpDown 0/1 [Ix] [Short Press] Pindhah Mudhun Rana Ngirim 1 (Mudhun)
1 bit C--T- DPT_UpDown 0/1 [Ix] [Short Press] Pindhah munggah/mudhun Rana Ngalih 0/1 (Munggah/Mudhun)
1 bit C--T- DPT_Langkah 0/1 [Ix] [Short Press] Stop/Step Up Shutter Ngirim 0 (Stop/Step Up)
1 bit C--T- DPT_Langkah 0/1 [Ix] [Short Press] Stop/Step Down Shutter Ngirim 1 (Stop/Step Down)
1 bit C--T- DPT_Langkah 0/1 [Ix] [Short Press] Stop/Step Shutter (Diuripake) Ngalih saka 0/1 (Stop/Step Up/Down)
4 bit C--T- DPT_Control_Dimming 0x0 (Detener) 0x1 (Reducir 100%)

0x7 (Reducir 1%) 0x8 (Detener) 0x9 (Subir 100%)

0xF (Subir 1%)
[Ix] [Short Press] Luwih padhang Tambah Padhang
4 bit C--T- DPT_Control_Dimming 0x0 (Detener) 0x1 (Reducir 100%)

0x7 (Reducir 1%) 0x8 (Detener) 0x9 (Subir 100%)

0xF (Subir 1%)
[Ix] [Short Press] Luwih peteng Ngurangi Padhang
4 bit C--T- DPT_Control_Dimming 0x0 (Detener) 0x1 (Reducir 100%)
… 0x7 (Reducir 1%) 0x8 (Detener) 0x9 (Subir 100%)… 0xF (Subir 1%)
[Ix] [Short Press] Padhang/Gelap Ngalih Padhang/Peteng
1 bit C--T- DPT_Ngalih 0/1 [Ix] [Short Press] Lampu On Ngirim 1 (Aktif)
1 bit C--T- DPT_Ngalih 0/1 [Ix] [Short Press] Lampu Mati Ngirim 0 (Mati)
1 bit I C – WT – DPT_Ngalih 0/1 [Ix] [Short Press] Lampu On/Off Ngalih 0/1
1 Byte C--T- DPT_SceneControl 0-63; 128-191 [Ix] [Short Press] Run Scene Ngirim saka 0 - 63
1 Byte C--T- DPT_SceneControl 0-63; 128-191 [Ix] [Short Press] Simpen Scene Ngirim saka 128 - 191
1 bit Aku/O CRWT – DPT_Ngalih 0/1 [Ix] [Switch/Sensor] Edge Ngirim 0 utawa 1
1 Byte C--T- DPT_Value_1_Ucount 0 – 255 [Ix] [Short Press] Nilai Konstan (Integer) 0 – 255
1 Byte C--T- DPT_Scaling 0% – 100% [Ix] [Short Press] Nilai Konstan (Persentage) 0% – 100%
2 bita C--T- DPT_Value_2_Ucount 0 – 65535 [Ix] [Short Press] Nilai Konstan (Integer) 0 – 65535
2 bita C--T- 9.xxx -671088,64 – 670433,28 [Ix] [Short Press] Nilai Konstan (Float) Nilai Ngambang
494, 500, 506, 512, 518, 524, 530, 536 1 Byte I C - W - - DPT_Scaling 0% – 100% [Ix] [Short Press] Status Rana (Input) 0% = Ndhuwur; 100% = Ngisor
1 Byte I C - W - - DPT_Scaling 0% – 100% [Ix] [Short Press] Status Dimming (Input) 0% – 100%
495, 501, 507, 513, 519, 525, 531, 537 1 bit C--T- DPT_Ngalih 0/1 [Ix] [Long Press] 0 Kiriman saka 0
1 bit C--T- DPT_Ngalih 0/1 [Ix] [Long Press] 1 Kiriman saka 1
1 bit I C – WT – DPT_Ngalih 0/1 [Ix] [Long Press] 0/1 Ngalih Ngalih 0/1
1 bit C--T- DPT_UpDown 0/1 [Ix] [Long Press] Pindhah munggah Rana Ngirim 0 (Up)
1 bit C--T- DPT_UpDown 0/1 [Ix] [Long Press] Pindhah Mudhun Rana Ngirim 1 (Mudhun)
1 bit C--T- DPT_UpDown 0/1 [Ix] [Long Press] Pindhah munggah/mudhun Rana Ngalih 0/1 (Munggah/Mudhun)
1 bit C--T- DPT_Langkah 0/1 [Ix] [Long Press] Stop/Step Up Shutter Ngirim 0 (Stop/Step Up)
1 bit C--T- DPT_Langkah 0/1 [Ix] [Long Press] Stop/Step Down Rana Ngirim 1 (Stop/Step Down)
1 bit C--T- DPT_Langkah 0/1 [Ix] [Long Press] Stop/Step Shutter (Diganti) Ngalih saka 0/1 (Stop/Step Up/Down)
4 bit C--T- DPT_Control_Dimming 0x0 (Detener) 0x1 (Reducir 100%)

0x7 (Reducir 1%) 0x8 (Detener) 0x9 (Subir 100%)

0xF (Subir 1%)
[Ix] [Long Press] Luwih padhang Long Pr. -> Luwih padhang; Release -> Stop
 

 

 

4 bit

 

 

 

C--T-

 

 

 

DPT_Control_Dimming

0x0 (Detener) 0x1 (Reducir 100%)

0x7 (Reducir 1%) 0x8 (Detener) 0x9 (Subir 100%)

0xF (Subir 1%)

 

 

 

[Ix] [Long Press] Luwih peteng
 

 

 

Long Pr. -> Luwih peteng; Release -> Stop

4 bit C--T- DPT_Control_Dimming 0x0 (Detener) 0x1 (Reducir 100%)

0x7 (Reducir 1%) 0x8 (Detener) 0x9 (Subir 100%)

0xF (Subir 1%)
[Ix] [Long Press] Padhang/Gelap Long Pr. -> Luwih padhang / luwih peteng; Ngeculake
-> Mungkasi
1 bit C--T- DPT_Ngalih 0/1 [Ix] [Long Press] Lampu On Ngirim 1 (Aktif)
1 bit C--T- DPT_Ngalih 0/1 [Ix] [Long Press] Lampu Mati Ngirim 0 (Mati)
1 bit I C – WT – DPT_Ngalih 0/1 [Ix] [Long Press] Lampu On/Off Ngalih 0/1
1 Byte C--T- DPT_SceneControl 0-63; 128-191 [Ix] [Long Press] Run Scene Ngirim saka 0 - 63
1 Byte C--T- DPT_SceneControl 0-63; 128-191 [Ix] [Long Press] Simpen Scene Ngirim saka 128 - 191
1 bit O CR - T - DPT_Weker 0/1 [Ix] [Ngalih/Sensor] Weker: Rusak utawa Sabotage 1 = Weker; 0 = Ora Weker
2 bita C--T- 9.xxx -671088,64 – 670433,28 [Ix] [Long Press] Nilai Konstan (Float) Nilai Ngambang
2 bita C--T- DPT_Value_2_Ucount 0 – 65535 [Ix] [Long Press] Nilai Konstan (Integer) 0 – 65535
1 Byte C--T- DPT_Scaling 0% – 100% [Ix] [Long Press] Nilai Konstan (Persentage) 0% – 100%
1 Byte C--T- DPT_Value_1_Ucount 0 – 255 [Ix] [Long Press] Nilai Konstan (Integer) 0 – 255
496, 502, 508, 514, 520, 526, 532, 538 1 bit C--T- DPT_Pemicu 0/1 [Ix] [Long Press/Release] Stop Shutter Release -> Stop Shutter
497, 503, 509, 515, 521, 527, 533, 539 1 Byte I C - W - - DPT_Scaling 0% – 100% [Ix] [Tekan Lama] Status Peredupan (Input) 0% – 100%
1 Byte I C - W - - DPT_Scaling 0% – 100% [Ix] [Tekan Lama] Status Rana (Input) 0% = Ndhuwur; 100% = Ngisor
540, 544, 548, 552, 556, 560, 564, 568 2 bita O CR - T - DPT_Value_Temp -273,00º – 670433,28º [Ix] Suhu Saiki Nilai Sensor Suhu
541, 545, 549, 553, 557, 561, 565, 569 1 bit O CR - T - DPT_Weker 0/1 [Ix] Overcooling 0 = Ora Weker; 1 = Weker
542, 546, 550, 554, 558, 562, 566, 570 1 bit O CR - T - DPT_Weker 0/1 [Ix] Overheating 0 = Ora Weker; 1 = Weker
543, 547, 551, 555, 559, 563, 567, 571 1 bit O CR - T - DPT_Weker 0/1 [Ix] Kasalahan Probe 0 = Ora Weker; 1 = Weker

Gabung lan kirim pitakon babagan piranti Zennio: https://support.zennio.com/

Zennio Avance lan Tecnologia SL
C/ Río Jarama, 132. Nave P-8.11
45007 Toledo (Spanyol).
Telp. +34 925 232 002
www.zennio.com
info@zennio.com

Dokumen / Sumber Daya

Zennio ZCL8H230V2 8/6/2 Output 230V Pemanasan Actuator [pdf] Manual pangguna
ZCL8H230V2 8 6 2 Output 230V Heating Actuator, ZCL8H230V2, 8 6 2 Output 230V Heating Actuator, Output 230V Heating Actuator, 230V Heating Actuator, Heating Actuator, Actuator

Referensi

Ninggalake komentar