SISTEM-SENSOR-LOGO

SISTEM SENSOR P2RL-SP Sirene karo Strobe Light

SISTEM-SENSOR-P2RL-SP-Sirene-karo-Strobe-Cahaya-PRODUCT

Informasi produk

  • Jeneng Produk: Perkakas Notifikasi Sensor Sistem
  • Nomer Model: P2RL, P2WL, P2RL-P, P2WL-P, P2RL-SP, P2WL-SP, P2GRL, P2GWL, CHSRL, CHSWL, SRL, SWL, SRL-P, SWL-P, SRL-SP, SWL-CLR -ALERT, SGRL, SGWL
  • Suhu Operasi: 10 nganti 93% Non-kondensasi
  • Strobo Flash Rate: 1 lampu kilat per detik
  • Nominal Voltage: Diatur 12VDC utawa diatur 24DC / FWR
  • Operasional Voltage Range: 8 kanggo 17.5V (12V nominal) utawa 16 kanggo 33V (24V nominal)
  • Operasional Voltage karo MDL3 Sync Module: 8.5 kanggo 17.5V (12V nominal) utawa 16.5 kanggo 33V (24V nominal)
  • Input Terminal Wire Gauge: 12 nganti 18 AWG Dimensi (Strobo Standar, Strobo Lonceng lan Strobo Tanduk): Dawa - 5.6" (143mm), Jembar - 4.7" (119mm), Dhuwur - 1.25" (32mm) Dimensi (Strobo Kompak lan Horn Horn Strobo): Dawa – 5.26″ (133 mm), Jembar – 3.46″ (88 mm), Ambane – 1.93″ (49 mm) Dimensi (Piranti standar karo SBBRL/WL Surface Mount Back Box): Dawane – 5.9″ (149 mm ), Jembar – 4.9″ (125 mm), ambane – 1.85″ (47 mm)
    Dimensi (Piranti kompak karo SBBGRL/WL Surface Mount Back Box): Dawane – 5.5″ (140 mm), Jembar – 3.7″ (94 mm), Dhuwur – 1.6″ (39 mm)

Pandhuan Panggunaan Produk

  1. Sadurunge nginstal, waca Pandhuan Referensi Aplikasi Audible Visible Sensor Sistem kanggo informasi rinci babagan piranti kabar, kabel, lan aplikasi khusus.
  2. Mirsani pedoman NFPA 72 lan NEMA nalika nginstal.
  3. Priksa manawa piranti notifikasi diuji lan dijaga miturut syarat NFPA 72.
  4. Perkakas kabar Sensor Sistem dirancang kanggo digunakake ing sistem 12 VDC, 24VDC, utawa 24V FWR.
  5. Perkakas bisa diaktifake dening panel kontrol weker geni utawa sumber daya sing kompatibel.
  6. Kanggo sinkronisasi, sambungake piranti menyang sumber daya sing bisa ngasilake pulsa sinkronisasi Sensor Sistem, output FACP NAC sing dikonfigurasi kanggo protokol sinkronisasi Sensor Sistem, utawa gunakake modul MDL3 kanggo ngasilake protokol sinkronisasi.

3825 Ohio Avenue, St. Charles, Illinois 60174
800/736-7672, FAX: 630/377-6495
www.systemsensor.com

Strobes Horn Output sing Bisa Dipilih, Strobo Lonceng lan Strobo - Wall Mount

  • Kanggo nggunakake model ing ngisor iki:
  • Strobo Tanduk Gunung Standar: P2RL, P2WL, P2RL-P, P2WL-P, P2RL-SP, P2WL-SP
  • Kompak Wall Mount Horn Strobe: P2GRL, P2GWL
  • Standard Wall Mount Chime Strobes: CHSRL, CHSWL
  • Strobo Pemasangan Dinding Standar: SRL, SWL, SRL-P, SWL-P, SRL-SP, SWL-CLR-ALERT
  • Kompak Wall Mount Strobes: SGRL, SGWL

SPESIFIKASI PRODUK

  • Suhu Operasional Standar: 32°F nganti 120°F (0°C nganti 49°C)
  • Range Kelembapan: 10 kanggo 93% Non-kondensasi Strobo Flash Rate 1 lampu kilat per detik
  • Nominal Voltage: Diatur 12VDC utawa diatur 24DC / FWR
  • Operasional Voltage Range: 8 nganti 17.5V (nominal 12V) utawa 16 nganti 33V (nominal 24V)
  • Operasional Voltage karo MDL3 Sync Module: 8.5 nganti 17.5V (nominal 12V) utawa 16.5 nganti 33V (nominal 24V)
  • Input terminal kawat gauge: 12 nganti 18 AWG

DIMENSI PRODUK lan AKSESORI

PRODUK DINDING dawa Jembar ambane
Strobo Standar, Strobo Lonceng lan Strobo Tanduk 5.6″ (143mm) 4.7″ (119mm) 1.25″ (32mm)
Strobo Kompak lan Strobo Tanduk 5.26" (133 mm) 3.46" (88 mm) 1.93 (49 mm)
Piranti standar karo SBBRL / WL Surface Mount Back Box 5.9" (149 mm) 4.9" (125 mm) 1.85" (47 mm)
Piranti kompak karo SBBGRL / WL Surface Mount Back Box 5.5" (140 mm) 3.7" (94 mm) 1.6" (39 mm)
CATETAN: SBBRL / WL lumahing Gunung Mbalik Box dimaksudaké mung kanggo strobes sungu standar, strobo chime lan strobes. SBBGRL / WL Surface Mount Back Box dimaksudaké kanggo strobes sungu kompak lan strobes.

PILIHAN KOTAK MOUNTING

  • Produk Indoor 2-Kawat Standar: 4″ x 4″ x 1½”, Gang Tunggal, Gang Ganda, 4″ Octagon, SBBRL/WL (tembok), SBBGRL/WL (tembok)
  • Produk Indoor 2-Kawat Kompak: Gang Tunggal, SBBGRL/WL (dinding)
  • WARTA: Manual iki kudu ditinggalake karo pemilik / pangguna peralatan iki.

Sadurunge nginstall

Mangga waca Pandhuan Referensi Aplikasi sing Bisa Dirungokake Sensor Sistem, sing nyedhiyakake informasi rinci babagan piranti kabar, kabel lan aplikasi khusus. Salinan manual iki kasedhiya saka Sensor Sistem. Pedoman NFPA 72 lan NEMA kudu diamati.
Penting: Piranti notifikasi sing digunakake kudu diuji lan dijaga miturut syarat NFPA 72.

GAMBARAN UMUM

Piranti kabar seri Sensor Sistem nawakake macem-macem piranti sing bisa dirungokake lan katon kanggo kabar safety urip. 2-kawat sungu strobe kita, strobo chime lan strobes teka karo 8 lapangan milih nada lan volume kombinasi lan 7 lapangan milih candela setelan. Ditujukake kanggo aplikasi njero ruangan lan disetujoni mung kanggo instalasi tembok. Kasedhiya ing loro desain soyo tambah atraktif, standar lan kompak (strobo sungu lan strobo mung). 2-kawat sungu strobe lan strobes iku piranti kabar mode umum dimaksudaké kanggo menehi tandha ing urip acara safety. Strobo lonceng 2 kabel minangka piranti notifikasi mode pribadi. Sungu wis kadhaptar kanggo ANSI / UL 464 syarat (mode umum) lan strobo kadhaptar kanggo ANSI / UL 1638 (mode umum). Strobo chime 2-kabel minangka piranti kabar mode pribadi sing dimaksudake kanggo menehi tandha marang personel sing dilatih kanggo neliti acara safety urip lan njupuk tindakan sing cocog. Bagean lonceng saka strobo lonceng kadhaptar menyang ANSI / UL 464 (mode pribadi) lan bagean strobo kadhaptar menyang ANSI / UL 1638 (mode pribadi). Perkakas kabar Sensor Sistem dirancang kanggo digunakake ing sistem 12 VDC, 24VDC, utawa 24V FWR (full wave rectified). Piranti AV Sensor Sistem bisa diaktifake dening panel kontrol weker geni utawa sumber daya sing kompatibel. Deleng produsen panel kontrol weker geni utawa sumber daya sing cocog kanggo informasi luwih lengkap.

Tembok Sensor Sistem strobo sungu 2-kabel, strobo lonceng 2-kabel, lan strobo sing kompatibel karo piranti kabar generasi sadurunge, wiwit 1996. Padha diaktifake karo protokol sinkronisasi Sensor Sistem sing mbutuhake sambungan menyang sumber daya sing bisa ngasilake pulsa sinkronisasi Sensor Sistem, output FACP NAC sing dikonfigurasi kanggo protokol sinkronisasi Sensor Sistem, utawa nggunakake modul MDL3 kanggo ngasilake protokol sinkronisasi.

PERTIMBANGAN SISTEM ALARM KEBAKARAN

Alarm Kebakaran Nasional lan Kode Sinyal, NFPA 72, mbutuhake kabeh piranti notifikasi, sing digunakake kanggo evakuasi bangunan sing dipasang sawise 1 Juli 1996, ngasilake sinyal kode temporal. Sinyal liyane saka sing digunakake kanggo tujuan evakuasi ora kudu ngasilake sinyal kode temporal. Sensor Sistem nyaranake jarak piranti notifikasi sing cocog karo NFPA 72.

DESIGN SISTEM

Desainer sistem kudu mesthekake yen total imbangan saiki dening piranti ing daur ulang ora ngluwihi kemampuan saiki saka sumber panel, lan piranti pungkasan ing sirkuit dilakokno ing volume sawijining.tage. Informasi tarik saiki kanggo nggawe petungan iki bisa ditemokake ing tabel ing manual. Kanggo penak lan akurasi, gunakake voltage gulung kalkulator ing Sensor Sistem websitus (www.systemsensor.com).
Nalika ngitung voltage kasedhiya kanggo piranti pungkasan, iku perlu kanggo nimbang voltage amarga resistance saka kabel. Sing luwih kenthel kabel, sing luwih cilik voltage drop. Tabel resistance kabel bisa dipikolehi saka buku tangan listrik. Elinga yen kabel Kelas A wis diinstal, dawa kabel bisa nganti kaping pindho minangka kanggo sirkuit sing ora fault tolerant. Jumlah total strobes ing NAC siji kudu ora ngluwihi 69 kanggo aplikasi 24 volt.

NADA NADA

Sensor Sistem nawakake macem-macem nada kanggo kabutuhan safety urip sampeyan, kalebu pola 3 temporal (½ detik on, ½ second off, ½ second on, ½ second off, ½ second on, 1½ off and repeat) sing ditemtokake dening ANSI lan NFPA 72 kanggo sinyal evakuasi darurat standar.
Kanggo milih nada, nguripake saklar rotary ing mburi prodhuk menyang setelan sing dikarepake. (Waca Gambar 1.)
Setelan sungu sing kasedhiya bisa ditemokake ing Tabel 1. Setelan chime sing kasedhiya bisa ditemokake ing Tabel 2.

TABEL 1. TUNDA TARUNG

Pos Nada Setelan Volume
1 Temporal dhuwur
2 Temporal kurang
3 Non Temporal dhuwur
4 Non Temporal kurang
5 3.1 KHz Temporal dhuwur
6 3.1 KHz Temporal kurang
7 3.1 KHz Non-Temporal dhuwur
8 3.1 KHz Non-Temporal kurang

TABEL 2. NADA KAMPUNG

Pos Nada Setelan Volume
1 1 Lonceng kapindho dhuwur
2 1 Lonceng kapindho kurang
3 1/4 Lonceng Kapindho dhuwur
4 1/4 Lonceng Kapindho kurang
5 Lonceng Temporal dhuwur
6 Lonceng Temporal kurang
7 5 Detik Wuh dhuwur
8 5 Detik Wuh kurang

SETTING CANDELA kasedhiya

Sistem Sensor nawakake macem-macem setelan candela kanggo kabutuhan safety urip. Kanggo milih output candela Panjenengan, nyetel ngalih geser ing mburi prodhuk menyang setelan candela dikarepake ing ngalih pamilih. (Waca Gambar 2.)
Setelan candela uga bisa diverifikasi kanthi ndeleng jendhela cilik ing ngarep unit. Waca Tabel 3 kanggo setelan candela kanggo produk tembok. Kabeh produk ketemu pro output cahyafiles kasebut ing UL Stan-dards cocok. (Waca Gambar 3 lan 4.)

DRAW saiki lan ratings swara

Kanggo strobo, gambar saiki kanggo saben setelan kadhaptar ing Tabel 3. Kanggo strobo sungu, gambar saiki lan setelan swara kadhaptar ing Tabel 4. Kanggo strobo chime, gambar saiki lan setelan swara kadhaptar ing Tabel 5.

SISTEM-SENSOR-P2RL-SP-Sirene-karo-Strobe-Cahaya-Gbr-1

TABEL 3. GAMBAR ARUS STROBO TEMBUNG (mA)

 

Candela

8-17.5

Volt

16-33 Volt
DC DC FWR
15 88 43 60
30 143 63 83
75 107 136
95 121 155
110 148 179
135 172 209
185 222 257

CATETAN: Produk sing disetel ing 15 lan 30 candela kanthi otomatis bisa digunakake ing sumber daya 12V utawa 24V. Produk ora kadhaptar kanggo operasi 12V DC nalika disetel menyang setelan candela liyane.

GAMBAR 3. OUTPUT LAMPU - DISPERSI HORIZONTAL

Derajat* Persen saka

Rating

0 100
5-25 90
30-45 75
50 55
55 45
60 40
65 35
70 35
75 30
80 30
85 25
90 25
Komponèn 45

ngiwa

24
Komponèn 45

ing sisih tengen

24

GAMBAR 4. DISPERSI VERTIKAL– TEMBOK TEMBUNG LANTAI

Derajat* Persen saka

Rating

0 100
5-30 90
35 65
40 46
45 34
50 27
55 22
60 18
65 16
70 15
75 13
80 12
85 12
90 12

SISTEM-SENSOR-P2RL-SP-Sirene-karo-Strobe-Cahaya-Gbr-2WIRING lan MOUNTING

Kabeh kabel kudu dipasang selaras karo Kode Listrik Nasional lan kode lokal uga wewenang sing duwe yurisdiksi. Wiring kudu ora dawa utawa ukuran kawat sing bisa nyebabake piranti kabar bisa digunakake ing njaba spesifikasi sing diterbitake. Sambungan sing ora bener bisa nyegah sistem supaya ora menehi tandha marang para penghuni yen ana kahanan darurat. Ukuran kabel nganti 12 AWG (2.5 mm°) bisa digunakake karo piring sing dipasang. Piring pemasangan dikirim kanthi terminal disetel kanggo kabel 12 AWG.
Nggawe sambungan kabel kanthi ngudani babagan 3/8″ insulasi saka ujung kabel. Banjur geser ujung kabel ing ngisor cl sing cocogamping piring lan kenceng clamping plate screw. We nyedhiyani guide strip kabel. Waca Figure 5 kanggo terminal wiring lan referensi guide Strip.

AWAS
Rampung pabrik ora kena diowahi: Aja dicet!

AWAS
Aja ngencengi sekrup piring sing dipasang; iki bisa nimbulaké piring soyo tambah kanggo lentur.

GAMBAR 5. TERMINAL WIRING, SHORTING SPRING, lan STRIP GUIDE

SISTEM-SENSOR-P2RL-SP-Sirene-karo-Strobe-Cahaya-Gbr-3

WIRING SISTEM

Strobo sungu 2-kabel, strobo chime lan strobo mung mbutuhake rong kabel kanggo daya lan pengawasan. (Waca Figure 6.) Mangga takon FACP manufacturer utawa pabrik sumber daya kanggo konfigurasi wiring tartamtu lan kasus khusus.

GAMBAR 6. 2-KAWAL SIRCUIT

SISTEM-SENSOR-P2RL-SP-Sirene-karo-Strobe-Cahaya-Gbr-4

SHORTING SPRING FITUR

Perkakas kabar Sensor Sistem teka karo spring shorting sing kasedhiya antarane terminal 2 lan 3 saka piring soyo tambah kanggo ngaktifake mriksa terus-terusan sistem sawise sistem wis kabel, nanging sadurunge instalasi saka produk final. (Waca Figure 5.) spring iki bakal kanthi otomatis disengage nalika produk wis diinstal, kanggo ngaktifake pengawasan saka sistem final.

MOUNTING

  1. Pasang piring soyo tambah menyang kothak prapatan. Plat pemasangan standar kompatibel karo 4 "kotak, geng tunggal, geng dobel, lan 4" octaging kothak prapatan. Piring pemasangan kompak kompatibel karo kothak persimpangan geng tunggal. (Deleng Gambar 7 lan 8.)
  2. Sambungake kabel lapangan miturut sebutan terminal. (Waca Gambar 5 lan 6.)
  3. Yen produk ora bakal diinstal ing titik iki, gunakake tutup bledug protèktif kanggo nyegah kontaminasi terminal kabel ing piring soyo tambah.
  4. Kanggo masang produk menyang piring soyo tambah, pancing tab ing ndhuwur omah produk menyang grooves ing soyo tambah piring. Banjur, nggeser produk menyangSISTEM-SENSOR-P2RL-SP-Sirene-karo-Strobe-Cahaya-Gbr-5

TABEL 4. TARUNG TARUNG TARUNG DINDING ARUS (mA) LAN OUTPUT Swara (dBA)

saiki nggambar (mA) Swara Output (dBA)
 

Pos

 

Nada

Volume Setelan 8-17.5 VDC 16-33 VDC 16-33 FWR 8-17.5 V 16-33 V
15 30 15 30 75 95 110 135 185 15 30 75 95 110 135 185 DC DC FWR
1 Temporal dhuwur 98 158 54 74 121 142 162 196 245 83 107 156 177 198 234 287 84 89 89
2 Temporal kurang 93 154 44 65 111 133 157 184 235 68 91 145 165 185 223 271 75 83 83
3 Non Temporal dhuwur 106 166 73 94 139 160 182 211 262 111 135 185 207 230 264 316 85 90 90
4 Non Temporal kurang 93 156 51 71 119 139 162 190 239 79 104 157 175 197 235 283 76 84 84
5 3.1 KHz Temporal dhuwur 93 156 53 73 119 140 164 190 242 81 105 155 177 196 234 284 83 88 88
6 3.1 KHz Temporal kurang 91 154 45 66 112 133 160 185 235 68 90 145 166 186 222 276 76 82 82
7 3.1 KHz Non-Temporal dhuwur 99 162 69 90 135 157 175 208 261 104 131 177 204 230 264 326 84 89 89
8 3.1 KHz Non-Temporal kurang 93 156 52 72 119 138 162 192 242 77 102 156 177 199 234 291 77 83 83

CATETAN: Produk sing disetel ing 15 lan 30 candela kanthi otomatis bisa digunakake ing sumber daya 12V utawa 24V. Produk ora kadhaptar kanggo operasi 12VDC nalika disetel menyang setelan candela liyane.

TABEL 5. DRAW ARUS STROBO CHIME DINDING (mA) LAN OUTPUT Swara (dBA)

saiki nggambar (mA) Swara Output (dBA)
 

Pos

 

lonceng Nada

Volume Setelan 8-17.5 VDC 16-33 VDC 16-33 FWR 8-17.5 V 16-33 V
15 30 15 30 75 95 110 135 185 15 30 75 95 110 135 185 DC DC FWR
1 1 Kapindho dhuwur 90 154 51 71 116 136 161 202 242 70 90 160 176 197 233 275 61 62 62
2 1 Kapindho kurang 89 154 50 70 115 136 154 199 238 67 88 158 175 191 232 271 56 55 55
3 1/4 Kapindho dhuwur 90 154 52 72 117 137 168 201 242 69 93 159 175 198 233 272 67 70 70
4 1/4 Kapindho kurang 89 153 49 70 115 136 165 199 241 68 93 154 169 196 232 270 61 61 61
5 Temporal dhuwur 88 153 49 69 112 137 168 201 246 65 90 145 170 189 228 283 64 66 66
6 Temporal kurang 88 152 47 68 111 136 167 196 241 64 89 142 170 188 219 282 59 60 60
7 5 Detik Wuh dhuwur 91 154 52 70 113 132 176 206 243 70 93 145 168 187 223 278 76 78 78
8 5 Detik Wuh kurang 87 149 46 66 108 130 170 202 240 62 84 137 159 180 216 272 62 64 64

CATETAN: Produk sing disetel ing 15 lan 30 candela kanthi otomatis bisa digunakake ing sumber daya 12V utawa 24V. Produk ora kadhaptar kanggo operasi 12VDC nalika disetel menyang setelan candela liyane.

posisi kanggo melu pin ing produk karo terminal ing piring soyo tambah. Priksa manawa tab ing mburi omah produk kebak karo piring soyo tambah.
5. Aman produk dening tightening siji soyo tambah meneng ing ngarep omah produk.

lumahing Gunung BACK BOX MOUNTING

  1. Kothak mburi gunung permukaan bisa diamanake langsung menyang tembok utawa langit-langit. A krenjang grounding karo kemampuan sekrup lemah diwenehake yen perlu. Kanggo piranti ukuran standar, deleng Gambar 9, lan kanggo piranti kompak, deleng Gambar 10.
  2. Kothak mburi dipasang ing tembok kudu dipasang kanthi panah munggah ngarah munggah. (Waca Gambar 12.)
  3. bolongan knockout Utas kasedhiya kanggo sisih kothak kanggo adaptor conduit ½ inci. Bolongan Knockout ing mburi kothak bisa digunakake kanggo mlebu mburi ½ inci.
  4. Kanggo mbusak knockout ½ inci, disaranake sampeyan nggunakake screw-driver flathead, selehake bilah saka screwdriver flat head ing pojok njero knockout. Ketuk obeng nalika sampeyan mlaku-mlaku kaya sing ditampilake ing Gambar 13.
    CATETAN: Kanggo ½ in. instalasi, ati-ati supaya ora nyerang knockout cedhak pojok ndhuwur kothak mburi gunung lumahing.
  5. V500 lan V700 raceway knockouts uga kasedhiya. Gunakake V500 kanggo pro kurangfile aplikasi lan V700 kanggo pro dhuwurfile aplikasi.
  6. Kanggo mbusak tang puteran kalah, kaya sing ditampilake ing Gambar 13.

TAMPER Skrup

Kanggo tamper resistance, meneng tawanan standar bisa diganti karo meneng Torx terlampir.

  1. Kanggo nyopot sekrup tawanan, bali metu sekrup lan tekanan ing mburi sekrup nganti dis-engages saka omah. Ganti karo meneng Torx diwenehake. (Waca Gambar 11.)SISTEM-SENSOR-P2RL-SP-Sirene-karo-Strobe-Cahaya-Gbr-6

    SISTEM-SENSOR-P2RL-SP-Sirene-karo-Strobe-Cahaya-Gbr-7

Mangga deleng sisipan kanggo Watesan Sistem Alarm Kebakaran

WARNING

Watesan saka sungu / STROBES

  • Sungu lan/utawa strobo ora bakal bisa tanpa daya. Tanduk / strobo entuk daya saka panel geni / keamanan ngawasi sistem weker. Yen daya dipateni kanggo alesan apa wae, sungu / strobo ora bakal menehi bebaya audio utawa visual sing dikarepake.
  • Klakson bisa uga ora keprungu. Swara klakson memenuhi (utawa ngluwihi) standar Underwriters Laboratories saiki. Nanging, sungu kasebut bisa uga ora menehi tandha marang wong sing turu utawa wong sing bubar nggunakake obat-obatan utawa ngombe minuman beralkohol. Klakson bisa uga ora keprungu yen diselehake ing lantai sing beda karo wong sing ana ing bebaya utawa yen dilebokake adoh banget kanggo keprungu amarga gangguan lingkungan kayata lalu lintas, AC, mesin utawa piranti musik sing bisa nyegah wong sing waspada ora krungu. weker.
  • Klakson bisa uga ora dirungokake dening wong sing duwe gangguan pangrungu.
    CATETAN: Strobes kudu dikuwasani terus-terusan kanggo operasi sungu.
  • Sinyal strobo bisa uga ora katon. Sinyal peringatan visual elektronik nggunakake tabung lampu kilat xenon sing bisa dipercaya. Kelip-kelip paling sethithik sapisan saben detik. Strobo kasebut ora kena dipasang ing sinar srengenge langsung utawa ing wilayah kanthi intensitas cahya sing dhuwur (luwih saka lilin 60 kaki) sing lampu kilat visual bisa diabaikan utawa ora katon. Strobo bisa uga ora katon dening wong tunanetra.
  • Sinyal strobo bisa nyebabake kejang. Wong sing duwe respon fotoik positif marang rangsangan visual kanthi kejang, kayata wong sing nandhang epilepsi, kudu ngindhari paparan sing suwe ing lingkungan sing sinyal strobo, kalebu strobo iki, diaktifake.
  • Sinyal strobo ora bisa operate saka sumber daya kode. Penyetor daya kode ngasilake daya sing diselani. Strobo kudu duwe sumber daya tanpa gangguan supaya bisa digunakake kanthi bener. Sistem Sensor nyaranake supaya sungu lan sinyal strobo tansah digunakake ing kombinasi supaya risiko saka watesan ing ndhuwur wis nyilikake.

JAMINAN TERBATAS TELU TAHUN

Sensor Sistem njamin produk sing dikumpulake bebas saka cacat ing bahan lan pengerjaan ing panggunaan lan layanan normal sajrone telung taun wiwit tanggal pabrik. Sensor Sistem ora menehi garansi nyata liyane kanggo produk iki. Ora ana agen, wakil, dealer, utawa karyawan Perusahaan sing nduweni wewenang kanggo nambah utawa ngowahi kewajiban utawa watesan saka Garansi iki. Kewajiban Perusahaan babagan Garansi iki diwatesi mung kanggo ngganti bagean produk sing ditemokake cacat ing bahan utawa karya ing panggunaan lan layanan normal sajrone telung taun wiwit tanggal pabrik. Sawise nelpon nomer bebas pulsa System Sensor 800-SENSOR2 (736-7672) kanggo nomer Otorisasi Pengembalian, kirimake unit sing rusak.tage prabayar kanggo: Honeywell, 12220 Rojas Drive, Suite 700, El Paso TX 79936.

Mangga kalebu cathetan njlentrehke malfunction lan seng di tuduh sabab saka Gagal. Perusahaan ora duwe kewajiban kanggo ngganti unit sing ditemokake cacat amarga karusakan, panggunaan sing ora wajar, modifikasi, utawa owah-owahan sing kedadeyan sawise tanggal pabrik. Ing kasus apa wae, Perusahaan ora bakal tanggung jawab kanggo ganti rugi konsekuensial utawa insidental amarga nglanggar Garansi iki utawa liyane, sing dituduhake utawa diwenehake, sanajan kerugian utawa karusakan kasebut disebabake dening kelalaian utawa kesalahan Perusahaan. Sawetara negara ora ngidini pengecualian utawa watesan kerusakan insidental utawa konsekuensial, mula watesan utawa pengecualian ing ndhuwur bisa uga ora ditrapake kanggo sampeyan. Warranty iki menehi hak legal tartamtu, lan sampeyan uga duwe hak liyane sing beda-beda saka negara kanggo negara.

PERNYATAAN FCC

Sistem Sensor Strobes lan Horn / Strobes wis dites lan ketemu kanggo tundhuk karo watesan kanggo piranti digital Kelas B, miturut bagean 15 saka Aturan FCC. Watesan kasebut dirancang kanggo menehi pangayoman sing cukup marang gangguan sing mbebayani nalika piranti kasebut dioperasikake ing lingkungan komersial. Peralatan iki ngasilake, nggunakake, lan bisa mancarake energi frekuensi radio lan, yen ora dipasang lan digunakake miturut instruksi manual, bisa nyebabake gangguan sing mbebayani kanggo komunikasi radio. Operasi peralatan iki ing wilayah omah bisa nyebabake gangguan sing mbebayani, saengga pangguna kudu mbenerake gangguan kasebut kanthi biaya dhewe.

System Sensor® minangka merek dagang kadhaptar saka Honeywell International, Inc.

I56-5845-001
©2017 Sistem Sensor. 01-12

3825 Ohio Avenue, St. Charles, Illinois 60174 800/736-7672, FAX: 630/377-6495
www.systemsensor.com

Dokumen / Sumber Daya

SISTEM SENSOR P2RL-SP Sirene karo Strobe Light [pdf] Pandhuan Instalasi
P2RL-SP, P2RL-SP Sirene nganggo Lampu Strobo, Sirene nganggo Lampu Strobo, Lampu Strobo, Lampu

Referensi

Ninggalake komentar

Alamat email sampeyan ora bakal diterbitake. Kolom sing dibutuhake ditandhani *