| OPERATOR PAGE PARAMETER |
| Paramèter |
Setelan (Nilai Default) |
| Wektu Mulai Command >>Wektu Abort Command >> |
Ya Ora (Default: Ora) |
| Interval Wektu (H:M) >> |
0.00 nganti 500.00 (HH:MM)(Default: 0.10) |
| Ctrl Set Value >> |
Setpoint LO limit menyang Setpoint HI limit (Default: 25.0) |
| Penyimpangan LO >> |
0.2 nganti 99.9 (Default: 2.0) |
| HI Penyimpangan >> |
0.2 nganti 99.9 (Default: 2.0) |
| Ganti Sandi >> |
1 nganti 100 (Default: 0) |
| SUPERVISORY > PARAMETER SERIAL |
| Paramèter |
Setelan (Nilai Default) |
| ID Piranti >> |
1 nganti 127 (Default: 1) |
| Baud Rate >> |
2400, 4800,9600, 19200,38400, 57600 (Default : 9600) |
| Paritas >> |
Ora Ana, Genap, Ganjil (Default: Genap) |
| Izin Tulis Serial >> |
Ora Ya (Default: Ora) |
| SUPERVISORY > SENSOR INPUT |
| Paramèter |
Setelan (Nilai Default) |
| Nul Offset >> |
-50.0 nganti 50.0 (Default: 0.0) |
| PENGAWASAN > KONTROL |
| Paramèter |
Setelan (Nilai Default) |
| Tune >> |
Ya Ora (Default: Ora) |
| Setpoint LO Limit >> |
Kanggo Input Thermocouple:-200 nganti Setpoint HI Limit Kanggo RTD Input:-99.9 nganti Setpoint HI Limit (Default: 0.0) |
| Setpoint Batas HI >> |
Kanggo Input Thermocouple: Setpoint LO Limit nganti 9999 Kanggo RTD Input: Setpoint LO Limit nganti 600.0(Default: 600.0) |
| Setpoint Kompresor >> |
0.0 nganti 100.0 (Default: 45.0) |
| Kompresor Hyst >> |
0.1 nganti 99.9 (Default: 2.0) |
| Heat Ctrl Action >> |
PID ON-OFF (Default: PID) |
| Heat Hyst >> |
0.1 nganti 99.9 (Default: 0.2) |
| Kalor Mung Kontrol |
Zona Kontrol Panas + Kelangan : Tunggal |
Zona Kontrol Panas + Kelangan : Dual |
| Band Proporsional >>0.1 nganti 999.9 (Default: 50.0) |
Band Proporsional >>0.1 nganti 999.9 (Default: 50.0) |
Cz Prop Band >> Band proporsional kanggo zona Pre-dominan Cool 0.1 nganti 999.9 (Default: 50.0) |
| Wektu Integral >> 0 nganti 3600 detik (Default: 100 detik) |
Wektu Integral >> 0 nganti 3600 detik (Default: 100 detik) |
Cz Wektu Integral >>Wektu Integral kanggo Cool Pre-dominan zone0 nganti 3600 detik (Default: 100 detik) |
| Wektu Turunan >>0 nganti 600 detik (Default: 16 detik) |
Wektu Turunan >>0 nganti 600 detik (Default: 16 detik) |
Cz Wektu Turunan >> Wektu Turunan kanggo Zona Pre-dominan Kelangan 0 nganti 600 detik (Default: 16 detik) |
| Kalor Mung Kontrol |
Zona Kontrol Panas + Kelangan : Tunggal |
Zona Kontrol Panas + Kelangan : Dual |
| Wektu Siklus >>0.5 nganti 100.0 detik (Default: 10.0 detik) |
Wektu Siklus >>0.5 nganti 100.0 detik (Default: 10.0 detik) |
Pita Prop Hz >> Band Proporsional kanggo zona Pre-dominan Panas 0.1 nganti 999.9 (Default: 50.0) |
| Overshoot Nyandhet >>Aktifake Pateni (Default: Pateni) |
Overshoot Nyandhet >>Aktifake Pateni (Default: Pateni) |
Wektu Integral Hz >>Wektu Integral kanggo zona Pre-dominan Panas0 nganti 3600 detik (Default: 100 detik) |
| Faktor Cutoff >>1.0 nganti 2.0 detik (Default: 1.2 detik) |
Faktor Cutoff >>1.0 nganti 2.0 detik (Default: 1.2 detik) |
Wektu Turunan Hz >> Wektu Turunan kanggo zona Pre-dominan Panas 0 nganti 600 detik (Default: 16 detik) |
| Wektu Siklus >>0.5 nganti 100.0 detik (Default: 10.0 detik) |
| Overshoot Nyandhet >> Aktifake Pateni (Default: Pateni) |
| Faktor Cutoff >>1.0 nganti 2.0 detik (Default: 1.2 detik) |
| SUPERVISORY > PASSWORD |
| Paramèter |
Setelan (Nilai Default) |
| Ganti Sandi >> |
1000 nganti 1999 (Default: 123) |
| PENGAWASAN > MUTU |
| Paramèter |
| Metu Mode Setup >> |
| PABRIK > SENSOR INPUT |
| Paramèter |
Setelan (Nilai Default) |
| Tipe Input >> |
Rujuk Tabel 1 (Default: RTD Pt100) |
| Filter Konstan >> |
0.5 nganti 60.0 (Default: 0.5) |
| PABRIK > PARAMETER ALARM |
| Paramèter |
Setelan (Nilai Default) |
| Histeresis >> |
0.1 nganti 99.9 (Default: 0.2) |
| Ngalangi >> |
Ya Ora (Default: Ya) |
| PABRIK > PILIH HEAT COOL |
| Paramèter |
Setelan (Nilai Default) |
| Strategi Kontrol >> |
Kalor Mung Kelangan Mung Kalor + Kelangan (Default: Kalor + Kelangan) |
| Strategi Kontrol: Mung Kelangan |
| Wektu Tundha (detik) >> |
0 nganti 1000 Detik (Default: 200 Detik) |
| Strategi Kontrol: Panas + Kelangan |
| Strategi Kompresor >> |
CONT. OFF CONT. ON SP BASED PV BASED(Default: SP BASED) |
| CONT. ON |
SP BASED |
PV BASED |
| WektuTundha (detik) >>0 nganti 1000 Detik (Default: 200 Detik) |
Nilai Set Wates >>0.0 nganti 100.0 (Default: 45.0) |
Kompresor SP >>0.0 nganti 100.0 (Default: 45.0) |
| Zona Kontrol >>Single Dual (Default: Single) |
WektuTundha (detik) >>0 nganti 1000 Detik (Default: 200 Detik) |
| WektuTundha (detik) >>0 nganti 1000 Detik (Default: 200 Detik) |
| PABRIK > PARAMETER TIMER |
| Paramèter |
Setelan (Nilai Default) |
| Aktifake >> |
Ora Ya (Default: Ora) |
| Mulai Band >> |
0 nganti 999.9 (Default: 0.5) |
| Strategi Holdback >> |
Ora Ana Mundhut Loro (Default: Ora Ana) |
| Tahan Band >> |
0.1 nganti 999.9 (Default: 0.5) |
| Panas Mati >> |
Ora Ya (Default: Ora) |
| Cool Off >> |
Ora Ya (Default: Ora) |
| Daya Recovery >> |
Batal Wiwiti maneh Terus (Default: Wiwiti maneh) |
| PABRIK > lawang mbukak |
| Paramèter |
Setelan (Nilai Default) |
| Aktifake >> |
Ya Ora (Default: Ora) |
| Ngalih Logika >> |
Tutup : Lawang Mbukak : Lawang Mbukak (Default : Tutup : Lawang Mbukak) |
| Lawang Alrm Dly (detik) >> |
0 nganti 1000 Detik (Default: 60 Detik) |
| PABRIK > PASSWORD |
| Paramèter |
Setelan (Nilai Default) |
| Ganti Sandi >> |
2000 nganti 2999 (Default: 321) |
| PABRIK > PABRIK DEFAULT |
| Paramèter |
Setelan (Nilai Default) |
| Setel menyang Default >> |
Ya Ora (Default: Ora) |
| PABRIK > MUTU |
| Paramèter |
| Metu Mode Setup >> |
| TABEL 1 |
| Pilihan |
Range (Min. nganti Maks.) |
Resolusi & Unit |
| Tipe J (Fe-K) |
0.0 nganti +960.0°C |
1 °C |
| Tipe K (Cr-Al) |
-200.0 nganti +1376.0 ° C |
| Tipe T (Cu-Con) |
-200.0 nganti +387.0 ° C |
| Tipe R (Rh-13%) |
0.0 nganti +1771.0°C |
| Tipe S (Rh-10%) |
0.0 nganti +1768.0°C |
| Tipe B |
0.0 nganti +1826.0°C |
| Tipe N |
0.0 nganti +1314.0°C |
| Reserved kanggo jinis Thermocouple khusus pelanggan sing ora kadhaptar ing ndhuwur. Jinis kasebut kudu ditemtokake miturut jinis termokopel sing dipesen (opsional ing panyuwunan). |
| RTD Pt100 |
-99.9 nganti +600.0 ° C |
0.1 °C |
| PV ERROR INDIKASI |
| Pesen |
Jinis Kesalahan |
sabab |
| BUKA |
Sensor mbukak |
RTD Pt100 / Thermocouple is Broken / Open |
| OVR |
Over-range |
Suhu ndhuwur Max. Range sing ditemtokake |
| UNR |
Under-range |
Suhu ngisor Min. Range sing ditemtokake |
| KUNCI PANEL NGAREP |
| Simbol |
Kunci |
Fungsi |
 |
Gulung |
Pencet kanggo nggulung macem-macem Layar Informasi Proses ing Mode Operasi Normal. |
 |
Weker Ngakoni |
Pencet kanggo ngakoni lan bisu (yen aktif) output weker. |
 |
TURUN |
Pencet kanggo nyuda nilai parameter. Pencet sapisan nyuda nilai kanthi siji count; terus dipencet nyepetake owah-owahan. |
 |
UP |
Pencet kanggo nambah nilai parameter. Pencet sapisan nambah nilai kanthi siji count; terus dipencet nyepetake owah-owahan. |
 |
UP-UP |
Pencet kanggo mlebu utawa metu saka mode persiyapan. |
 |
ENTER |
Pencet kanggo nyimpen nilai parameter sing disetel lan kanggo nggulung menyang parameter sabanjure. |
SAMBUNGAN LISTRIK

| OPERATOR PAGE PARAMETER |
| Paramèter |
Setelan (Nilai Default) |
| Wektu Mulai Command >>Wektu Abort Command >> |
Ya Ora (Default: Ora) |
| Interval Wektu (H:M) >> |
0.00 nganti 500.00 (HH:MM)(Default: 0.10) |
| Ctrl Set Value >> |
Setpoint LO limit menyang Setpoint HI limit (Default: 25.0) |
| Penyimpangan LO >> |
0.2 nganti 99.9 (Default: 2.0) |
| HI Penyimpangan >> |
0.2 nganti 99.9 (Default: 2.0) |
| Ganti Sandi >> |
1 nganti 100 (Default: 0) |
| SUPERVISORY > SENSOR INPUT |
| Paramèter |
Setelan (Nilai Default) |
| Nul Offset >> |
-50.0 nganti 50.0 (Default: 0.0) |
| SUPERVISORY > PARAMETER SERIAL |
| Paramèter |
Setelan (Nilai Default) |
| ID Piranti >> |
1 nganti 127 (Default: 1) |
| Baud Rate >> |
2400, 4800,9600, 19200,38400, 57600 (Default : 9600) |
| Paritas >> |
Ora Ana, Genap, Ganjil (Default: Genap) |
| Izin Tulis Serial >> |
Ora Ya (Default: Ora) |
| PENGAWASAN > KONTROL |
| Paramèter |
Setelan (Nilai Default) |
| Tune >> |
Ya Ora (Default: Ora) |
| Setpoint LO Limit >> |
Kanggo Input Thermocouple:-200 nganti Setpoint HI Limit Kanggo RTD Input:-99.9 nganti Setpoint HI Limit (Default: 0.0) |
| Setpoint Batas HI >> |
Kanggo Input Thermocouple: Setpoint LO Limit nganti 9999 Kanggo RTD Input: Setpoint LO Limit nganti 600.0(Default: 600.0) |
| Setpoint Kompresor >> |
0.0 nganti 100.0 (Default: 45.0) |
| Kompresor Hyst >> |
0.1 nganti 99.9 (Default: 2.0) |
| Heat Ctrl Action >> |
PID ON-OFF (Default: PID) |
| Heat Hyst >> |
0.1 nganti 99.9 (Default: 0.2) |
| Kalor Mung Kontrol |
Zona Kontrol Panas + Kelangan : Tunggal |
Zona Kontrol Panas + Kelangan : Dual |
| Band Proporsional >>0.1 nganti 999.9 (Default: 50.0) |
Band Proporsional >>0.1 nganti 999.9 (Default: 50.0) |
Cz Prop Band >> Band proporsional kanggo zona Pre-dominan Cool 0.1 nganti 999.9 (Default: 50.0) |
| Wektu Integral >> 0 nganti 3600 detik (Default: 100 detik) |
Wektu Integral >> 0 nganti 3600 detik (Default: 100 detik) |
Cz Wektu Integral >>Wektu Integral kanggo Cool Pre-dominan zone0 nganti 3600 detik (Default: 100 detik) |
| Wektu Turunan >>0 nganti 600 detik (Default: 16 detik) |
Wektu Turunan >>0 nganti 600 detik (Default: 16 detik) |
Cz Wektu Turunan >> Wektu Turunan kanggo Zona Pre-dominan Kelangan 0 nganti 600 detik (Default: 16 detik) |
| Kalor Mung Kontrol |
Zona Kontrol Panas + Kelangan : Tunggal |
Zona Kontrol Panas + Kelangan : Dual |
| Wektu Siklus >>0.5 nganti 100.0 detik (Default: 10.0 detik) |
Wektu Siklus >>0.5 nganti 100.0 detik (Default: 10.0 detik) |
Pita Prop Hz >> Band Proporsional kanggo zona Pre-dominan Panas 0.1 nganti 999.9 (Default: 50.0) |
| Overshoot Nyandhet >>Aktifake Pateni (Default: Pateni) |
Overshoot Nyandhet >>Aktifake Pateni (Default: Pateni) |
Wektu Integral Hz >>Wektu Integral kanggo zona Pre-dominan Panas0 nganti 3600 detik (Default: 100 detik) |
| Faktor Cutoff >>1.0 nganti 2.0 detik (Default: 1.2 detik) |
Faktor Cutoff >>1.0 nganti 2.0 detik (Default: 1.2 detik) |
Wektu Turunan Hz >> Wektu Turunan kanggo zona Pre-dominan Panas 0 nganti 600 detik (Default: 16 detik) |
| Wektu Siklus >>0.5 nganti 100.0 detik (Default: 10.0 detik) |
| Overshoot Nyandhet >> Aktifake Pateni (Default: Pateni) |
| Faktor Cutoff >>1.0 nganti 2.0 detik (Default: 1.2 detik) |
| SUPERVISORY > PASSWORD |
| Paramèter |
Setelan (Nilai Default) |
| Ganti Sandi >> |
1000 nganti 1999 (Default: 123) |
| PENGAWASAN > MUTU |
| Paramèter |
Setelan (Nilai Default) |
| Metu Mode Setup >> |
Ya Ora (Default: Ora) |
| PABRIK > SENSOR INPUT |
| Paramèter |
Setelan (Nilai Default) |
| Tipe Input >> |
Rujuk Tabel 1 (Default: RTD Pt100) |
| Filter Konstan >> |
0.5 nganti 60.0 (Default: 0.5) |
| PABRIK > PARAMETER ALARM |
| Paramèter |
Setelan (Nilai Default) |
| Histeresis >> |
0.1 nganti 99.9 (Default: 0.2) |
| Ngalangi >> |
Ya Ora (Default: Ya) |
| PABRIK > PILIH HEAT COOL |
| Paramèter |
Setelan (Nilai Default) |
| Strategi Kontrol >> |
Kalor Mung Kelangan Mung Kalor + Kelangan (Default: Kalor + Kelangan) |
| Strategi Kontrol: Mung Kelangan |
| Wektu Tundha (detik) >> |
0 nganti 1000 Detik (Default: 200 Detik) |
| Strategi Kontrol: Panas + Kelangan |
| Strategi Kompresor >> |
CONT. OFF CONT. ON SP BASED PV BASED(Default: CONT. ON) |
| CONT. ON |
SP BASED |
PV BASED |
| WektuTundha (detik) >>0 nganti 1000 Detik (Default: 200 Detik) |
Nilai Set Wates >>0.0 nganti 100.0 (Default: 45.0) |
Kompresor SP >>0.0 nganti 100.0 (Default: 45.0) |
| Zona Kontrol >>Single Dual (Default: Single) |
WektuTundha (detik) >>0 nganti 1000 Detik (Default: 200 Detik) |
| WektuTundha (detik) >>0 nganti 1000 Detik (Default: 200 Detik) |
| PABRIK > PARAMETER TIMER |
| Paramèter |
Setelan (Nilai Default) |
| Aktifake >> |
Ora Ya (Default: Ora) |
| Mulai Band >> |
0 nganti 999.9 (Default: 0.5) |
| Strategi Holdback >> |
Ora Ana Mundhut Loro (Default: Ora Ana) |
| Tahan Band >> |
0.1 nganti 999.9 (Default: 0.5) |
| Panas Mati >> |
Ora Ya (Default: Ora) |
| Cool Off >> |
Ora Ya (Default: Ora) |
| Daya Recovery >> |
Batal Wiwiti maneh Terus (Default: Wiwiti maneh) |
| PABRIK > lawang mbukak |
| Paramèter |
Setelan (Nilai Default) |
| Aktifake >> |
Ya Ora (Default: Ora) |
| Ngalih Logika >> |
Tutup : Lawang Mbukak : Lawang Mbukak (Default : Tutup : Lawang Mbukak) |
| Lawang Alrm Dly (detik) >> |
0 nganti 1000 Detik (Default: 60 Detik) |
| PABRIK > PASSWORD |
| Paramèter |
Setelan (Nilai Default) |
| Ganti Sandi >> |
2000 nganti 2999 (Default: 321) |
| PABRIK > PABRIK DEFAULT |
| Paramèter |
Setelan (Nilai Default) |
| Setel menyang Default >> |
Ya Ora (Default: Ora) |
| PABRIK > MUTU |
| Paramèter |
Setelan (Nilai Default) |
| Metu Mode Setup >> |
Ya Ora (Default: Ora) |
| TABEL 1 |
| Pilihan |
Range (Min. nganti Maks.) |
Resolusi & Unit |
| Tipe J (Fe-K) |
0.0 nganti +960.0°C |
1 °C |
| Tipe K (Cr-Al) |
-200.0 nganti +1376.0 ° C |
| Tipe T (Cu-Con) |
-200.0 nganti +387.0 ° C |
| Tipe R (Rh-13%) |
0.0 nganti +1771.0°C |
| Tipe S (Rh-10%) |
0.0 nganti +1768.0°C |
| Tipe B |
0.0 nganti +1826.0°C |
| Tipe N |
0.0 nganti +1314.0°C |
| Reserved kanggo jinis Thermocouple khusus pelanggan sing ora kadhaptar ing ndhuwur. Jinis kasebut kudu ditemtokake miturut jinis termokopel sing dipesen (opsional ing panyuwunan). |
| RTD Pt100 |
-99.9 nganti +600.0 ° C |
0.1 °C |
| PV ERROR INDIKASI |
| Pesen |
Jinis Kesalahan |
sabab |
| BUKA |
Sensor mbukak |
RTD Pt100 / Thermocouple is Broken / Open |
| OVR |
Over-range |
Suhu ndhuwur Max. Range sing ditemtokake |
| UNR |
Under-range |
Suhu ngisor Min. Range sing ditemtokake |
| KUNCI PANEL NGAREP |
| Simbol |
Kunci |
Fungsi |
 |
Gulung |
Pencet kanggo nggulung macem-macem Layar Informasi Proses ing Mode Operasi Normal. |
 |
Weker Ngakoni |
Pencet kanggo ngakoni lan bisu (yen aktif) output weker. |
 |
TURUN |
Pencet kanggo nyuda nilai parameter. Pencet sapisan nyuda nilai kanthi siji count; terus dipencet nyepetake owah-owahan. |
 |
UP |
Pencet kanggo nambah nilai parameter. Pencet sapisan nambah nilai kanthi siji count; terus dipencet nyepetake owah-owahan. |
 |
UP-UP |
Pencet kanggo mlebu utawa metu saka mode persiyapan. |
 |
ENTER |
Pencet kanggo nyimpen nilai parameter sing disetel lan kanggo nggulung menyang parameter sabanjure. |
SAMBUNGAN LISTRIK

Dhukungan
101, Diamond Industrial Estate, Navghar,
Jalan Vasai (E), Kab. Palghar – 401 210.
Dodolan : 8208199048 / 8208141446
Dhukungan : 07498799226 / 08767395333
E: sales@ppiindia.net, support@ppiindia.net