SPESIFIKASI

SPESIFIKASI
sumber daya Voltage 10-38 V DC; 10-28 V AC
konsumsi daya 2,4 W @ 24 V DC 3 VA @ 24 V AC
Input digital 16x, logika "0": 0-3 V, logis "1": 6-36 V
Counter 16x, Resolusi 32 bit Frekuensi maks 1 kHz
Non-volatile counter memory (FRAM)
Isolasi galvanik Max 1500 V rms
Antarmuka RS485, nganti 128 piranti ing bis
baud rate Saka 2400 nganti 115200 bps
Ingress Protection IP40 – kanggo instalasi njero ruangan
Suhu Operasi -10°C – +50°C; Panyimpenan - 40 ° C - + 85 ° C
Kelembapan Relatif 5 nganti 95% RH (tanpa kondensasi)
Konektor Max 2.5 mm2
ukuran 119,1 mm x 101 mm x 22,6 mm
Pemasangan Pemasangan rel DIN (DIN EN 50022)
Material omah Plastik, PC / ABS sing mateni dhewe

PITUDUHiSMACONTROLLI-SFAR-S-16DI-M-Modbus-Input-and-Output-Module-FIG-2

WARNING 

  • Elinga, kabel produk sing salah bisa ngrusak lan nyebabake bebaya liyane. Priksa manawa produk wis disambungake kanthi bener sadurunge nguripake daya.
  • Sadurunge masang kabel, utawa nyopot/nyopot produk, pesthekake mateni daya. Gagal nglakoni bisa nyebabake kejut listrik.
  • Aja ndemek bagean sing diisi daya kayata terminal daya. Mengkono bisa nyebabake kejut listrik.
  • Aja mbongkar prodhuk. Mengkono bisa nyebabake kejut listrik utawa operasi sing rusak.
  • Gunakake produk ing kisaran operasi sing disaranake ing spesifikasi (suhu, kelembapan, voltage, kejut, arah pemasangan, atmosfer lsp). Gagal nglakoni bisa nyebabake geni utawa operasi sing rusak.
  • Kencengake kabel menyang terminal. Kenceng kabel sing ora cukup menyang terminal bisa nyebabake geni

TERMINAL saka piranti iSMACONTROLLI-SFAR-S-16DI-M-Modbus-Input-and-Output-Module-FIG-3

Akses kadhaptar

Modbus Dec Hex Jeneng Register Akses Katrangan
30001 0 0x00 Versi / Jinis maca Versi lan jinis piranti
30002 1 0x01 Ngalih maca Ngalih negara
40003 2 0x02 Baud rate Maca & Nulis Tingkat baud RS485
40004 3 0x03 Stop Bits & Data Bits Maca & Nulis Jumlah bit mandeg & bit data (waca
40005 4 0x04 Paritas Maca & Nulis Paritas bit
40006 5 0x05 Tundha Tanggepan Maca & Nulis Tundha respon ing ms
40007 6 0x06 Modbus Mode Maca & Nulis Mode Modbus (ASCII utawa RTU)
40018 17 0x11 Filter input Maca & Nulis Konfigurasi filter input
 

40033

 

32

 

0x20

Paket Ditampa LSR (Least Significant Reg.)  

Maca & Nulis

 

 

Jumlah paket sing ditampa

 

40034

 

33

 

0x21

Paket sing ditampa MSR (Reg. Paling Penting)  

Maca & Nulis

40035 34 0x22 Paket LSR salah Maca & Nulis  

Jumlah paket sing ditampa kanthi kesalahan

40036 35 0x23 Paket MSR salah Maca & Nulis
40037 36 0x24 Paket dikirim LSR Maca & Nulis  

Jumlah paket sing dikirim

40038 37 0x25 Paket dikirim MSR Maca & Nulis
30051 50 0x32 Input maca Negara input
40053 52 0x34 Konter 1 LSR Maca & Nulis  

32-bit counter 1

40054 53 0x35 Konter 1 MSR Maca & Nulis
40055 54 0x36 Konter 2 LSR Maca & Nulis  

32-bit counter 2

40056 55 0x37 Konter 2 MSR Maca & Nulis
40057 56 0x38 Konter 3 LSR Maca & Nulis  

32-bit counter 3

40058 57 0x39 Konter 3 MSR Maca & Nulis
40059 58 0x3A Konter 4 LSR Maca & Nulis  

32-bit counter 4

40060 59 0x3b Konter 4 MSR Maca & Nulis
40061 60 0x3c Konter 5 LSR Maca & Nulis  

32-bit counter 5

40062 61 0x3d Konter 5 MSR Maca & Nulis
40063 62 0x3E Konter 6 LSR Maca & Nulis  

32-bit counter 6

40064 63 0x3f Konter 6 MSR Maca & Nulis
40065 64 0x40 Konter 7 LSR Maca & Nulis  

32-bit counter 7

40066 65 0x41 Konter 7 MSR Maca & Nulis
40067 66 0x42 Konter 8 LSR Maca & Nulis  

32-bit counter 8

40068 67 0x43 Konter 8 MSR Maca & Nulis
40069 68 0x44 Konter 9 LSR Maca & Nulis  

32-bit counter 9

40070 69 0x45 Konter 9 MSR Maca & Nulis
Modbus Dec Hex Jeneng Register Akses Katrangan
40071 70 0x46 Konter 10 LSR Maca & Nulis  

32-bit counter 10

40072 71 0x47 Konter 10 MSR Maca & Nulis
40073 72 0x48 Konter 11 LSR Maca & Nulis  

32-bit counter 11

40074 73 0x49 Konter 11 MSR Maca & Nulis
40075 74 0x4A Konter 12 LSR Maca & Nulis  

32-bit counter 12

40076 75 0x4b Konter 12 MSR Maca & Nulis
40077 76 0x4c Konter 13 LSR Maca & Nulis  

32-bit counter 13

40078 77 0x4d Konter 13 MSR Maca & Nulis
40079 78 0x4E Konter 14 LSR Maca & Nulis  

32-bit counter 14

40080 79 0x4f Konter 14 MSR Maca & Nulis
40081 80 0x50 Konter 15 LSR Maca & Nulis  

32-bit counter 15

40082 81 0x51 Konter 15 MSR Maca & Nulis
40083 82 0x52 Konter 16 LSR Maca & Nulis  

32-bit counter 16

40084 83 0x53 Konter 16 MSR Maca & Nulis
40085 84 0x54 CCcounter 1 LSR Maca & Nulis  

Nilai 32-bit counter sing dijupuk 1

40086 85 0x55 CCcounter 1 MSR Maca & Nulis
40087 86 0x56 CCcounter 2 LSR Maca & Nulis  

Nilai 32-bit counter sing dijupuk 2

40088 87 0x57 CCcounter 2 MSR Maca & Nulis
40089 88 0x58 CCcounter 3 LSR Maca & Nulis  

Nilai 32-bit counter sing dijupuk 3

40090 89 0x59 CCcounter 3 MSR Maca & Nulis
40091 90 0x5A CCcounter 4 LSR Maca & Nulis  

Nilai 32-bit counter sing dijupuk 4

40092 91 0x5b CCcounter 4 MSR Maca & Nulis
40093 92 0x5c CCcounter 5 LSR Maca & Nulis  

Nilai 32-bit counter sing dijupuk 5

40094 93 0x5d CCcounter 5 MSR Maca & Nulis
40095 94 0x5E CCcounter 6 LSR Maca & Nulis  

Nilai 32-bit counter sing dijupuk 6

40096 95 0x5f CCcounter 6 MSR Maca & Nulis
40097 96 0x60 CCcounter 7 LSR Maca & Nulis  

Nilai 32-bit counter sing dijupuk 7

40098 97 0x61 CCcounter 7 MSR Maca & Nulis
40099 98 0x62 CCcounter 8 LSR Maca & Nulis  

Nilai 32-bit counter sing dijupuk 8

40100 99 0x63 CCcounter 8 MSR Maca & Nulis
40101 100 0x64 CCcounter 9 LSR Maca & Nulis  

Nilai 32-bit counter sing dijupuk 9

40102 101 0x65 CCcounter 9 MSR Maca & Nulis
40103 102 0x66 CCcounter 10 LSR Maca & Nulis  

Nilai 32-bit counter sing dijupuk 10

40104 103 0x67 CCcounter 10 MSR Maca & Nulis
Modbus Dec Hex Jeneng Register Akses Katrangan
40105 104 0x68 CCcounter 11 LSR Maca & Nulis  

Nilai 32-bit counter sing dijupuk 11

40106 105 0x69 CCcounter 11 MSR Maca & Nulis
40107 106 0x6A CCcounter 12 LSR Maca & Nulis  

Nilai 32-bit counter sing dijupuk 12

40108 107 0x6b CCcounter 12 MSR Maca & Nulis
40109 108 0x6c CCcounter 13 LSR Maca & Nulis  

Nilai 32-bit counter sing dijupuk 13

40110 109 0x6d CCcounter 13 MSR Maca & Nulis
40111 110 0x6E CCcounter 14 LSR Maca & Nulis  

Nilai 32-bit counter sing dijupuk 14

40112 111 0x6f CCcounter 14 MSR Maca & Nulis
40113 112 0x70 CCcounter 15 LSR Maca & Nulis  

Nilai 32-bit counter sing dijupuk 15

40114 113 0x71 CCcounter 15 MSR Maca & Nulis
40115 114 0x72 CCcounter 16 LSR Maca & Nulis  

Nilai 32-bit counter sing dijupuk 16

40116 115 0x73 CCcounter 16 MSR Maca & Nulis
40117 116 0x74 Konfigurasi Counter 1 Maca & Nulis  

 

 

 

 

 

Konfigurasi Counter

 

+1 - pangukuran wektu (yen 0 ngitung impuls)

+2 - counter nyekel otomatis saben 1 detik

+4 - nilai nyekel nalika input kurang

+8 - ngreset counter sawise nyekel

+16 - ngreset counter yen input kurang

+32 - ngodhe

40118 117 0x75 Konfigurasi Counter 2 Maca & Nulis
40119 118 0x76 Konfigurasi Counter 3 Maca & Nulis
40120 119 0x77 Konfigurasi Counter 4 Maca & Nulis
40121 120 0x78 Konfigurasi Counter 5 Maca & Nulis
40122 121 0x79 Konfigurasi Counter 6 Maca & Nulis
40123 122 0x7A Konfigurasi Counter 7 Maca & Nulis
40124 123 0x7b Konfigurasi Counter 8 Maca & Nulis
40125 124 0x7c Konfigurasi Counter 9 Maca & Nulis
40126 125 0x7d Konfigurasi Counter 10 Maca & Nulis
40127 126 0x7E Konfigurasi Counter 11 Maca & Nulis
40128 127 0x7f Konfigurasi Counter 12 Maca & Nulis
40129 128 0x80 Konfigurasi Counter 13 Maca & Nulis
40130 129 0x81 Konfigurasi Counter 14 Maca & Nulis
40131 130 0x82 Konfigurasi Counter 15 Maca & Nulis
40132 131 0x83 Konfigurasi Counter 16 Maca & Nulis
40133 132 0x84 nyekel Maca & Nulis Counter nyekel
40134 133 0x85 Status Maca & Nulis Dijupuk counter

PEDOMAN INSTALASI

iSMACONTROLLI-SFAR-S-16DI-M-Modbus-Input-and-Output-Module-FIG-4Waca pandhuan sadurunge nggunakake utawa ngoperasikake piranti. Yen ana pitakonan sawise maca dokumen iki, hubungi Tim Dhukungan iSMA CONTROLLI
(support@ismacontrolli.com).

iSMACONTROLLI-SFAR-S-16DI-M-Modbus-Input-and-Output-Module-FIG-5

  • Sadurunge nyopot utawa nyopot produk, priksa manawa mateni daya. Gagal nglakoni bisa nyebabake kejut listrik.
  • Kabel produk sing ora bener bisa ngrusak lan nyebabake bebaya liyane. Priksa manawa produk wis disambungake kanthi bener sadurunge nguripake daya.
  • Aja ndemek bagean sing diisi daya kayata terminal daya. Mengkono bisa nyebabake kejut listrik.
  • Aja mbongkar prodhuk. Mengkono bisa nyebabake kejut listrik utawa operasi sing salah.iSMACONTROLLI-SFAR-S-16DI-M-Modbus-Input-and-Output-Module-FIG-6
  • Gunakake produk mung ing kisaran operasi sing disaranake ing spesifikasi (suhu, kelembapan, voltage, kejut, arah pemasangan, atmosfer, lsp). Gagal nglakoni bisa nyebabake geni utawa operasi sing rusak.
  • Kencengake kabel menyang terminal. Gagal nglakoni bisa nyebabake geni.
  • Aja masang produk ing cedhak piranti lan kabel listrik daya dhuwur, beban induktif, lan piranti ngoper. Cedhak obyek kasebut bisa nyebabake gangguan sing ora bisa dikendhaleni, nyebabake operasi produk sing ora stabil.
  • Pengaturan daya lan kabel sinyal sing tepat mengaruhi operasi kabeh sistem kontrol. Aja nyelehake kabel daya lan sinyal ing tray kabel paralel. Bisa nyebabake gangguan ing sinyal sing diawasi lan kontrol.
  • Disaranake kanggo kontrol daya / modul karo supplier daya AC / DC. Padha nyedhiyakake insulasi sing luwih apik lan luwih stabil kanggo piranti dibandhingake karo sistem trafo AC / AC, sing ngirimake gangguan lan fenomena transien kaya lonjakan lan bledosan menyang piranti. Dheweke uga ngisolasi produk saka fenomena induktif saka trafo lan beban liyane.
  • Sistem sumber daya kanggo produk kudu dilindhungi dening piranti eksternal sing mbatesi overvoltage lan efek saka discharge kilat.
  • Aja nguwasani produk lan piranti sing dikontrol/dipantau, utamane daya dhuwur lan beban induktif, saka siji sumber daya. Piranti daya saka sumber daya siji nyebabake risiko ngenalke gangguan saka beban menyang piranti kontrol.
  • Yen trafo AC / AC digunakake kanggo nyuplai piranti kontrol, disaranake nggunakake trafo Kelas 100 2 VA maksimal kanggo ngindhari efek induktif sing ora dikarepake, sing mbebayani kanggo piranti.
  • Garis ngawasi lan kontrol sing dawa bisa nyebabake puteran ing sambungan karo sumber daya sing dienggo bareng, nyebabake gangguan ing operasi piranti, kalebu komunikasi eksternal. Disaranake nggunakake separator galvanik.
  • Kanggo nglindhungi sinyal lan jalur komunikasi marang interferensi elektromagnetik eksternal, gunakake kabel lan manik-manik ferrite sing grounded kanthi bener.
  • Ngalih relay output digital saka beban induktif gedhe (ngluwihi spesifikasi) bisa nyebabake pulsa gangguan menyang elektronik sing dipasang ing njero produk. Mulane, disaranake nggunakake relay eksternal / kontaktor, lan liya-liyane kanggo ngalih beban kasebut. Panggunaan pengontrol karo output triac uga mbatesi overvol sing padhatage fenomena.
  • Akeh kasus gangguan lan overvoltage ing sistem kontrol kui dening ngalih, beban induktif diwenehake dening voltage (AC 120/230 V). Yen ora duwe sirkuit pangurangan swara sing cocog, disaranake nggunakake sirkuit eksternal kayata snubber, varistor, utawa dioda proteksi kanggo mbatesi efek kasebut.

Instalasi listrik produk iki kudu ditindakake miturut kode kabel nasional lan tundhuk karo peraturan lokal.
iSMA CONTROLLI SpA – Via Carlo Levi 52, 16010 Sant'Olcese (GE) – Italia | support@ismacontrolli.com
www.ismacontrolli.com