DELTA-logo

DELTA DVP04PT-S PLC Analog Input Output Modul

DELTA-DVP04PT-S-PLC-Analog-Input-Output-Module-product

Spesifikasi

  • Model: DVP04/06PT-S
  • Input: 4/6 titik RTDs
  • Output: sinyal digital 16-bit
  • Instalasi: Kabinet kontrol bebas bledug, kelembapan, kejut listrik, lan geter
  • Ukuran: 90.00mm x 60.00mm x 25.20mm
  • Piranti jinis mbukak
  • Unit daya kapisah

Pandhuan Panggunaan Produk

Pedoman Instalasi

  • Priksa manawa kabinet kontrol bebas saka bledug, kelembapan, kejut listrik, lan geter.
  • Gunakake pangayoman kanggo nyegah akses utawa kacilakan sing ora sah.
  • Aja nyambungake daya AC menyang terminal I/O.

Nguatake

  • Priksa maneh kabeh kabel sadurunge nguripake piranti.
  • Aja ndemek terminal apa wae sak menit sawise medhot piranti.
  • Lemah terminal kanthi bener kanggo nyegah gangguan elektromagnetik.

Wiring Eksternal

  • Tindakake diagram kabel sing kasedhiya ing manual kanggo sambungan sing bener.
  • Gunakake kabel sing dilindhungi kanggo integritas sinyal sing luwih apik.
  • Tansah kabel minangka cendhak sabisa kanggo nyuda gangguan gangguan.

Pambuka

Matur nuwun kanggo milih Delta DVP seri PLC. DVP04 / 06PT-S bisa nampa 4/6 TCTerms saka RTDs lan Ngonversi menyang sinyal digital 16-dicokot. Liwat instruksi FROM / TO ing program MPU seri DVP Slim, data bisa diwaca lan ditulis. Ana akeh 16-bit kontrol register (CR) ing modul. Unit daya kasebut kapisah lan ukurane cilik lan gampang dipasang.

DVP04/06PT-S minangka piranti OPEN-TYPE. Sampeyan kudu dipasang ing lemari kontrol sing bebas saka bledug, kelembapan, kejut listrik lan geter. Kanggo nyegah staf non-pangopènan saka operasi DVP04 / 06PT-S, utawa kanggo nyegah kacilakan saka ngrusak DVP04 / 06PT-S, kabinèt kontrol kang DVP04 / 06PT-S diinstal kudu dilengkapi karo pangayoman. Kanggo example, kabinèt kontrol kang DVP04 / 06PT-S diinstal bisa dikunci karo alat khusus utawa tombol.

Aja nyambungake daya AC menyang terminal I/O, yen ora, karusakan serius bisa kedadeyan. Mangga dipriksa maneh kabeh kabel sadurunge DVP04/06PT-S diuripake. Sawise DVP04 / 06PT-S pedhot, Aja tutul terminal sembarang ing menit. Priksa manawa terminal lemah DELTA-DVP04PT-S-PLC-Analog-Input-Output-Module-fig-4ing DVP04 / 06PT-S wis grounded bener kanggo nyegah gangguan elektromagnetik.

Pro Produkfile & Ukuran

DELTA-DVP04PT-S-PLC-Analog-Input-Output-Module-fig-1

1. Indikator status (POWER, RUN and ERROR) 2. Jeneng model 3. DIN ril klip
4. terminal I / O 5. Indikator titik I/O 6. Bolongan sing dipasang
7. Label spesifikasi 8. port sambungan modul I / O 9. klip modul I/O
10. Rel DIN (35mm) 11. klip modul I/O 12. Port komunikasi RS-485 (DVP04PT-S)
13. Port sambungan daya
(DVP04PT-S)
14. port sambungan I / O  

Wiring

Tata Letak Terminal I/O

DELTA-DVP04PT-S-PLC-Analog-Input-Output-Module-fig-2

Wiring Eksternal

DELTA-DVP04PT-S-PLC-Analog-Input-Output-Module-fig-3

Cathetan

  • Gunakake mung kabel sing wis dikempalken karo sensor suhu kanggo input analog lan misahake saka saluran listrik liyane utawa kabel sing bisa nimbulaké gangguan.
  • Sensor RTD 3-kabel nyedhiyakake daur ulang ganti rugi sing bisa digunakake kanggo nyuda resistensi kabel nalika sensor RTD 2-kabel ora duwe mekanisme kanggo ngimbangi. Gunakake kabel (3-kabel) kanthi dawa sing padha (kurang saka 200 m) lan resistensi kabel kurang saka 20 ohm.
  • Yen ana gangguan, sambungake kabel sing dilindhungi menyang titik bumi sistem, banjur lemah titik bumi sistem utawa sambungake menyang kothak distribusi.
  • Mangga tetep kabel minangka cendhak sabisa nalika nyambungake modul kanggo piranti kang suhu bakal diukur, lan supaya kabel daya digunakake adoh saka kabel disambungake kanggo mbukak sabisa kanggo nyegah gangguan gangguan.
  • Mangga nyambung DELTA-DVP04PT-S-PLC-Analog-Input-Output-Module-fig-4ing modul sumber daya lan DELTA-DVP04PT-S-PLC-Analog-Input-Output-Module-fig-4ing modul suhu kanggo lemah sistem, lan banjur lemah sistem lemah utawa nyambung lemah sistem kanggo kothak distribusi.

Spesifikasi

Spesifikasi Listrik

Maks. konsumsi daya dirating 2W
Operasi / panyimpenan Operasi: 0°C~55°C (suhu), 5~95% (kelembapan), tingkat polusi 2

Panyimpenan: -25°C~70°C (suhu), 5~95% (kelembapan)

Tahan geter / kejut Standar internasional: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC 68-2-27 (TEST Ea)
 

Sambungan seri menyang DVP- PLC MPU

Modul kasebut diwenehi nomer saka 0 nganti 7 kanthi otomatis kanthi jarak saka MPU. No.0 sing paling cedhak karo MPU lan No.7 sing paling adoh. maksimal

8 modul diijini kanggo nyambung menyang MPU lan ora Occupy sembarang digital I / O TCTerms.

Spesifikasi Fungsional

DVP04/06PT-S Celcius (°C) Fahrenheit (°F)
Saluran input analog 4/6 saluran saben modul
Tipe sensor 2-kawat/3-kawat Pt100 / Pt1000 3850 PPM/°C (DIN 43760 JIS C1604-1989)

/ Ni100 / Ni1000 / LG-Ni1000 / Cu100 / Cu50/ 0~300Ω/ 0~3000Ω

Eksitasi saiki 1.53mA / 204.8uA
Range input suhu Mangga deleng kurva karakteristik suhu/nilai digital.
Range konversi digital Mangga deleng kurva karakteristik suhu/nilai digital.
Resolusi 0.1°C 0.18°F
Akurasi sakabèhé ± 0.6% saka skala lengkap sajrone 0 ~ 55°C (32 ~ 131°F)
Wektu nanggepi DVP04PT-S: 200ms / saluran; DVP06PT-S: 160/ms/saluran
Metode isolasi

(antarane sirkuit digital lan analog)

Ora ana isolasi ing antarane saluran.

500VDC antarane sirkuit digital/analog lan Ground 500VDC antarane sirkuit analog lan sirkuit digital 500VDC antarane 24VDC lan Ground

Format data digital 2's komplemen 16-bit
Fungsi rata-rata Ya (DVP04PT-S: CR#2 ~ CR#5 / DVP06PT-S: CR#2)
Fungsi diagnostik dhewe Saben saluran duwe fungsi deteksi wates ndhuwur / ngisor.
 

 

Mode Komunikasi RS-485

Didhukung, kalebu mode ASCII/RTU. Format komunikasi standar: 9600, 7, E, 1, ASCII; waca CR # 32 kanggo rincian babagan format komunikasi.

Cathetan 1: RS-485 ora bisa digunakake nalika disambungake menyang PLC seri CPU. Cathetan2: Waca Slim Type Special Module Communications ing lampiran E manual program DVP kanggo rincian liyane babagan persiyapan komunikasi RS-485.

* 1: Unit suhu bakal ditampilake minangka 0.1 ° C / 0.1 ° F. Yen unit suhu disetel dadi Fahrenheit, panggonan desimal kapindho ora bakal ditampilake.

Register kontrol

CR# alamat Dicekel Atribut Ndhaptar isi Katrangan
#0 H'4064 O R Jeneng model

(Setelan dening sistem)

Kode model DVP04PT-S = H'8A

Kode model DVP06PT-S = H'CA

 

 

 

 

 

 

 

 

#1

 

 

 

 

 

 

 

 

H'4065

 

 

 

 

 

 

 

 

X

 

 

 

 

 

 

 

 

R/W

 

 

 

 

 

 

 

 

Setelan Mode CH1~CH4

b15~12 b11~8 b7~4 b3~0
CH4 CH3 CH2 CH1
Njupuk mode CH1 (b3,b2,b1,b0) contoneample.

1. (0,0,0,0): Pt100 (standar)

2. (0,0,0,1): Ni100

3. (0,0,1,0): Pt1000

4. (0,0,1,1): Ni1000

5. (0,1,0,0): LG-Ni1000

6. (0,1,0,1): Cu100

7. (0,1,1,0): Cu50

8. (0,1,1,1): 0~300 Ω

9. (1,0,0,0): 0~3000 Ω

10. (1,1,1,1)Saluran dipateni.

Mode 8 lan 9 mung kasedhiya kanggo DVP04PT-S V4.16 utawa mengko lan

DVP06PT-S V4.12 utawa mengko.

 

 

 

 

#2

 

 

H'4066

 

 

 

 

O

 

 

 

 

R/W

 

DVP04PT-S:

Angka rata-rata CH1

Piece nomer wacan digunakake kanggo pitungan suhu "rata-rata" ing CH1.

Range setelan: K1~K20. Setelan standar yaiku K10.

 

 

 

DVP06PT-S:

CH1~CH6 angka rata-rata

Nomer potongan sing digunakake kanggo pitungan suhu "rata-rata" ing CH1 ~ 6.

Range setelan: K1~K20. Setelan standar yaiku K10.

 

 

#3

 

 

H'4067

 

 

O

 

 

H'4067

 

DVP04PT-S:

Angka rata-rata CH2

Piece nomer wacan digunakake kanggo pitungan suhu "rata-rata" ing CH2.

Range setelan: K1~K20. Setelan standar yaiku K10.

 

 

#4

 

 

H'4068

 

 

O

 

 

H'4068

 

DVP04PT-S:

Angka rata-rata CH3

Piece nomer wacan digunakake kanggo pitungan suhu "rata-rata" ing CH3.

Range setelan: K1~K20. Setelan standar yaiku K10.

 

#5

 

H'4069

 

O

 

H'4069

 

DVP04PT-S:

Angka rata-rata CH4

Piece nomer wacan digunakake kanggo pitungan suhu "rata-rata" ing CH4.

Range setelan: K1~K20.
Setelan standar yaiku K10.

#6 H'406A X R CH1 derajat rata-rata DVP04PT-S:

Derajat rata-rata kanggo CH1 ~ 4 DVP06PT-S:

Rata-rata derajat kanggo CH1 ~ 6

Unit: 0.1°C, 0.01 Ω (0~300 Ω), 0.1 Ω (0~3000 Ω)

#7 H'406B X R CH2 derajat rata-rata
#8 H'406C X R CH3 derajat rata-rata
#9 H'406D X R CH4 derajat rata-rata
#10 X R CH5 derajat rata-rata
#11 X R CH6 derajat rata-rata
#12 H'4070 X R CH1 derajat rata-rata DVP04PT-S:

Derajat rata-rata kanggo CH1 ~ 4 DVP06PT-S:

Gelar rata-rata kanggo CH1 ~ 6 Unit: 0.1°F, 0.01 Ω (0~300 Ω), 0.1 Ω (0~3000 Ω)

#13 H'4071 X R CH2 derajat rata-rata
#14 H'4072 X R CH3 derajat rata-rata
#15 H'4073 X R CH4 derajat rata-rata
#16 X R CH5 derajat rata-rata
#17 X R CH6 derajat rata-rata
#18 H'4076 X R Saiki suhu. saka CH1 DVP04PT-S:

Suhu saiki CH 1~4 DVP06PT-S:

Suhu saiki CH1~6 Unit: 0.1°C, 0.01 Ω (0~300 Ω),

0.1 Ω (0~3000 Ω)

#19 H'4077 X R Saiki suhu. saka CH2
#20 H'4078 X R Saiki suhu. saka CH3
#21 H'4079 X R Saiki suhu. saka CH4
#22 X R Saiki suhu. saka CH5
#23 X R Saiki suhu. saka CH6
#24 H'407C X R Saiki suhu. saka CH1  

DVP04PT-S:

Suhu saiki CH 1~4

DVP06PT-S:

Suhu saiki CH 1~6 Unit: 0.1°F, 0.01 Ω (0~300 Ω),

0.1 Ω (0~3000 Ω)

#25 H'407D X R Saiki suhu. saka CH2
#26 H'407E X R Saiki suhu. saka CH3
#27 H'407F X R Saiki suhu. saka CH4
#28 X R Saiki suhu. saka CH5
#29 X R Saiki suhu. saka CH6
 

#29

 

H'4081

 

X

 

R/W

 

DVP04PT-S:

Setelan mode PID

Setel H'5678 minangka mode PID lan nilai liyane minangka mode normal

Nilai standar yaiku H'0000.

 

#30

 

H'4082

 

X

 

R

 

Status kesalahan

Register data nyimpen status kesalahan. Deleng grafik kode kesalahan kanggo rincian.
 

 

#31

 

H'4083

 

O

 

R/W

DVP04PT-S:

Setelan alamat komunikasi

Setel alamat komunikasi RS-485; sawetara setelan: 01~254.

Default: K1

 

 

X

 

R/W

DVP06PT-S:

Setelan Mode CH5~CH6

Mode CH5: b0 ~ b3 Mode CH6: b4 ~ b7

Waca CR # 1 kanggo referensi

 

 

 

 

 

 

 

 

 

32

 

 

 

 

 

 

H'4084

 

 

 

 

 

 

O

 

 

 

 

 

 

R/W

 

 

 

 

 

DVP04PT-S:

Setelan format komunikasi

Kanggo baud rate, setelan 4,800/9,600/19,200/38,400/57,600/ 115,200 bps.

Format komunikasi:

ASCII: 7,E,1/7,O,1/8,E,1/8,O,1

/ 8,N,1

RTU: 8,E,1 / 8,O,1 / 8,N,1

Default pabrik: ASCII,9600,7,E,1 (CR#32=H'0002)

Deleng setelan format komunikasi ※CR#32 ing mburi tabel iki kanggo informasi luwih lengkap.

 

 

 

 

 

 

X

 

 

 

R/W

 

 

DVP06PT-S: CH5~CH6

Kesalahan setelan indikator LED

b15~12 b11~9 b8~6 b5~3 b2~0
ERR

LED

dilindhungi undhang-undhang CH6 CH5
b12 ~ 13 cocog karo CH5 ~ 6, nalika bit ON, ukurane ngluwihi jangkoan, lan indikator LED Error sumunar.
 

 

#33

 

 

H'4085

 

 

O

 

 

R/W

DVP04PT-S: CH1~CH4

Reset menyang setelan gawan Lan setelan Indikator LED kesalahan

 
b15~12 b11~9 b8~6 b5~3 b2~0
ERR

LED

CH4 CH3 CH2 CH1
Yen b2~b0 disetel dadi 100, kabeh nilai setelan CH1 bakal direset
   

 

 

 

 

 

 

 

X

 

 

 

 

R/W

 

 

DVP06PT-S:

CH1~CH4 Reset menyang setelan gawan Lan CH1~CH4 Error LED indikator setelan

menyang standar. Kanggo ngreset kabeh saluran menyang standar, nyetel b11 ~ 0 kanggo H'924 (DVP04PT-S ndhukung siji lan kabeh saluran reset; DVP06PT- S mung ndhukung kabeh saluran). b12~15 cocog karo CH1~4, nalika bit ON, ukurane ngluwihi

jangkoan, lan Indikator LED Error kelip-kelip.

#34 H'4086 O R Versi firmware Tampilan versi ing heksadesimal. contone:

H'010A = versi 1.0A

#35 ~ #48 Kanggo nggunakake sistem
Simbol: O tegese digantung. (Didhukung nganggo RS485, nanging ora ndhukung nalika nyambungake menyang MPU.)

X tegese ora kenceng. R tegese bisa maca data kanthi nggunakake instruksi FROM utawa RS-485. W tegese bisa nulis data kanthi nggunakake instruksi TO utawa RS-485.

  1. Added fungsi RESET mung kanggo 04PT-S modul karo perangkat kukuh V4.16 utawa mengko lan ora kasedhiya kanggo 06PT-S. Sambungake input daya modul kanggo 24 VDC lan nulis H'4352 menyang CR # 0 lan banjur mateni daya lan urip maneh; kabeh paramèter ing modul, kalebu paramèter komunikasi dibalèkaké menyang standar pabrik.
  2. Yen sampeyan pengin nggunakake alamat Modbus ing format desimal, sampeyan bisa nransfer ndhaftar heksadesimal menyang format desimal lan banjur nambah siji supaya dadi alamat ndhaftar Modbus desimal. Kanggo example nransfer alamat "H'4064" saka CR # 0 ing format heksadesimal kanggo format desimal, duwe asil 16484 lan banjur nambah siji menyang, sampeyan duwe 16485, alamat Modbus ing format desimal.
  3. Setelan format komunikasi CR # 32: kanggo modul DVP04PT-S karo perangkat kukuh V4.14 utawa versi sadurungé, b11~b8 pilihan format data ora kasedhiya. Kanggo mode ASCII, format kasebut tetep dadi 7, E, 1 (H'00XX) lan kanggo mode RTU, format kasebut tetep dadi 8, E, 1 (H'C0xx/H'80xx). Kanggo modul karo perangkat kukuh V4.15 utawa mengko, deleng tabel ing ngisor iki kanggo persiyapan. Elinga yen kode asli H'C0XX / H'80XX bakal katon minangka RTU, 8, E, 1 kanggo modul karo perangkat kukuh V4.15 utawa mengko.
b15 ~ b12 b11 ~ b8 b7 ~ b0
ASCII / RTU, ngganti bait kurang lan dhuwur saka kode mriksa CRC  

Format data

 

Baud rate

Katrangan
H'0 ASCII H'0 7,E,1*1 H'01 4800 bps
 

H'8

RTU,

aja ijolan kode cek CRC sing kurang lan dhuwur

H'1 8,E,1 H'02 9600 bps
H'2 dilindhungi undhang-undhang H'04 19200 bps
 

H'C

RTU,

ngganti bait kurang lan dhuwur saka kode mriksa CRC

H'3 8, N, 1 H'08 38400 bps
H'4 7,O,1*1 H'10 57600 bps
  H'5 8.O,1 H'20 115200 bps

Cathetan * 1: Iki mung kasedhiya kanggo format ASCII.
contone: Tulis H'C310 menyang CR # 32 kanggo asil saka RTU, ngganti bait kurang lan dhuwur saka kode mriksa CRC, 8,N,1 lan baud rate ing 57600 bps.

  1. Kode fungsi RS-485: 03'H kanggo maca data saka register. 06'H kanggo nulis tembung data kanggo ndaftar. 10'H kanggo nulis sawetara tembung data kanggo ndhaftar.
  2. CR # 30 minangka ndhaptar kode kesalahan.
    • Cathetan: Saben kode kesalahan bakal duwe bit sing cocog lan kudu diowahi dadi angka biner 16-bit (Bit0~15). Loro utawa luwih kesalahan bisa kedadeyan bebarengan. Deleng grafik ing ngisor iki:
Nomer bit 0 1 2 3
 

Katrangan

Sumber daya ora normal Kontak ora disambungake menyang apa-apa.  

dilindhungi

 

dilindhungi

Nomer bit 4 5 6 7
Katrangan dilindhungi dilindhungi kesalahan nomer rata-rata Kesalahan instruksi
Nomer bit 8 9 10 11
Katrangan CH1 Konversi abnormal CH2 Konversi abnormal CH3 Konversi abnormal CH4 Konversi abnormal
Nomer bit 12 13 14 15
Katrangan CH5 Konversi abnormal CH6 Konversi abnormal dilindhungi dilindhungi
  1. Kurva Karakteristik Suhu/Nilai Digital

Mode pangukuran suhu Celsius (Fahrenheit):

DELTA-DVP04PT-S-PLC-Analog-Input-Output-Module-fig-5

Sensor Kisaran suhu Range konversi nilai digital
°C (Min./Maks.) °F (Min./Maks.) °C (Min./Maks.) °F (Min./Maks.)
Pt100 -180 ~ 800°C -292 ~ 1,472°F K-1,800 ~ K8,000 K-2,920 ~ K14,720
Ni100 -80 ~ 170°C -112 ~ 338°F K-800 ~ K1,700 K-1,120 ~ K3,380
Pt1000 -180 ~ 800°C -292 ~ 1,472°F K-1,800 ~ K8,000 K-2,920 ~ K14,720
Ni1000 -80 ~ 170°C -112 ~ 338°F K-800 ~ K1,700 K-1,120 ~ K3,380
LG-Ni1000 -60 ~ 200°C -76 ~ 392°F K-600 ~ K2,000 K-760 ~ K3,920
Cu100 -50 ~ 150°C -58 ~ 302°F K-500 ~ K1,500 K-580 ~ K3,020
Cu50 -50 ~ 150°C -58 ~ 302°F K-500 ~ K1,500 K-580 ~ K3,020
Sensor Range resistor input Range konversi nilai digital
0~300Ω 0Ω ~ 320Ω K0 ~ 32000 0~300Ω 0Ω ~ 320Ω
0~3000Ω 0Ω ~ 3200Ω K0 ~ 32000 0~3000Ω 0Ω ~ 3200Ω
  1. Nalika CR # 29 disetel kanggo H'5678, CR # 0 ~ CR # 34 bisa digunakake kanggo setelan PID karo DVP04PT-S versi V3.08 lan ndhuwur.

FAQ

  • Q: Apa bisa nyambungake daya AC menyang terminal I/O?
    • A: Ora, nyambungake daya AC menyang sembarang terminal I/O bisa nimbulaké karusakan serius. Tansah mriksa kabel sadurunge ngisi daya.
  • Q: Kepiye cara nangani piranti kasebut sawise dicopot?
    • A: Sawise medhot piranti, aja ndemek terminal apa wae paling sethithik sak menit kanggo njamin keamanan.
  • Q: Apa sing kudu ditindakake kanggo nyegah gangguan elektromagnetik?
    • A: Pesthekake yen terminal lemah ing piranti wis grounded bener kanggo nyegah gangguan elektromagnetik.

Dokumen / Sumber Daya

DELTA DVP04PT-S PLC Analog Input Output Modul [pdf] Pandhuan
DVP04PT-S, DVP06PT, DVP04PT-S PLC Modul Input Output Analog, DVP04PT-S, Modul Output Input Analog PLC, Modul Output Input Analog, Modul Output Input, Modul Output, Modul

Referensi

Ninggalake komentar

Alamat email sampeyan ora bakal diterbitake. Kolom sing dibutuhake ditandhani *